18
Manual – MOVIDRIVE® MDX61B MOVI-PLC® DHP11B Control Card
3
Connecting PROFIBUS (connector X30)
Assembly / Installation Instructions
Setting the
station address
The PROFIBUS station address is set using DIP switches 2
0
... 2
6
on the DHP11B
control card.
The DHP11B control card supports the address range 0...125.
Any change made to the PROFIBUS station address during ongoing operation does not
take effect immediately. You have to switch off the drive inverter with the DHP11B and
on again for the changes to take effect (power + 24 V off/on).
20056AXX
The default setting for the PROFIBUS station address is 4:
2
0
→
Significance: 1
×
0 = 0
2
1
→
Significance: 2
×
0 = 0
2
2
→
Significance: 4
×
1 = 4
2
3
→
Significance: 8
×
0 = 0
2
4
→
Significance: 16
×
0 = 0
2
5
→
Significance: 32
×
0 = 0
2
6
→
Significance: 64
×
0 = 0
DHP11B
X31
X32
X33
X30
X34
2
0
2
1
2
2
2
3
2
4
2
5
2
6