19
3
Connection of RS485 interface (connector X34)
Assembly / Installation Instructions
3.7
Connection of RS485 interface (connector X34)
The RS485 interface enables you to interconnect up to 32 units.
You can connect the following devices to the RS485 interface:
•
Engineering PC, or
•
DOP11A operator terminal, or
•
A maximum of three MOVIMOT
®
gearmotors with integrated frequency inverter
Wiring diagram RS485 interface
Cable specification
•
Use a 4-core twisted and shielded copper cable (data transmission cable with
braided copper shield). The cable must meet the following specifications:
– Core cross section 0.25 ... 0.75 mm
2
(AWG 23 ... 18)
– Cable resistance 100 ... 150
Ω
at 1 MHz
– Capacitance per unit length
≤
40 pF/m at 1 kHz
For example, the following cable is suitable:
– BELDEN (www.belden.com), data cable type 3105A
Shielding
•
Connect the shield to the electronics shield clamp on the inverter or higher-level con-
troller and make sure it is connected over a wide area at both ends.
Cable length
•
The permitted total cable length is 200 m.
Terminating
resistor
•
Dynamic terminating resistors are installed. Do not connect any external terminat-
ing resistors.
57356AXX
Figure 8: RS485 connection taking the example of a MOVIDRIVE
®
MDX60B/61B drive inverter
X3
4
2
0
2
1
2
2
2
3
2
4
2
5
2
6
1
MDX61B
RS
+
2
1
5V
DHP11B
RS
-
DGND
3
4
24V
R
L
f1/f2
K1a
K1b
RS-
RS+
MOVIDIVE
®
24V
R
L
f1/f2
K1a
K1b
RS-
RS+
MOVIMOT
®
MOVIMOT
®
There must not be any difference of potential between the units connected with the
RS485. Take suitable measures to avoid potential displacement, such as connecting the
unit ground connectors using a separate cable.
For more information on how to connect the DOP11A operator terminal, refer to the sec-
tions "Installation" and "Pin assignment" in the "DOP11A Operator Terminals" manual.