6
Service
Fault messages and list of faults
Compact Operating Instructions – MOVIDRIVE
®
MDX60B/61B
44
Fault
Subfault
Code Designation Response
(P)
Code
Designation
Possible cause
Measure
109
DCS alarm
Display fault 0
DCS alarm
1
Communication fault back-
plane bus MOVIDRIVE
®
B.
The DCS..B option does not re-
ceive any valid data from
MOVIDRIVE
®
B.
• Check hardware connection
to MOVIDRIVE
®
B.
• Check firmware version of
MOVIDRIVE
®
B.
• Apply braided shield of en-
coder cable, motor cable,
and TF cable over a large
area.
• Establish equipotential
bonding.
2
Pulse 1 plausibility fault at
digital input DI1.
The configured pulse 1 voltage
is not present at digital input
DI1 (X81:2).
• Check configuration of the
DI1 digital input according
to configuration and wiring
diagram.
• Check the wiring.
3
4
Pulse 1 plausibility fault at
digital input DI2.
The configured pulse 1 voltage
is not present at digital input
DI2 (X81:3).
• Check configuration of the
DI2 digital input according
to configuration and wiring
diagram.
• Check the wiring.
5
6
Pulse 1 plausibility fault at
digital input DI3.
The configured pulse 1 voltage
is not present at digital input
DI3 (X81:4).
• Check configuration of the
DI3 digital input according
to configuration and wiring
diagram.
• Check the wiring.
7
8
Pulse 1 plausibility fault at
digital input DI4.
The configured pulse 1 voltage
is not present at digital input
DI4 (X81:5).
• Check configuration of the
DI4 digital input according
to configuration and wiring
diagram.
• Check the wiring.
9
24770531/EN – 11/2017