6
Service
Fault messages and list of faults
Compact Operating Instructions – MOVIDRIVE
®
MDX60B/61B
54
Fault
Subfault
Code Designation Response
(P)
Code
Designation
Possible cause
Measure
196
Power sec-
tion
Immediate
stop
1
Discharge resistor
Discharge resistor overload
Observe waiting time for
power on/off
2
Hardware ID precharge/
discharge control
Incorrect precharge/discharge
controller variant
• Consult SEW Service
• Replace precharge/dis-
charge control
3
Inverter coupling
Defective inverter coupling
• Consult SEW Service
• Replace inverter coupling
4
Inverter coupling reference
voltage
Defective inverter coupling
• Consult SEW Service
• Replace inverter coupling
5
Power sections configura-
tion
Different phase modules in-
stalled in the unit
• Inform the SEW Service
• Check and replace phase
modules
6
Control unit configuration
Control unit line inverter or mo-
tor inverter incorrect
Replace or correctly assign
the control unit of line and mo-
tor inverter
7
Communication power
section control unit
No communication
Check control unit installation
8
Communication pre-
charge/discharge control
inverter coupling
No communication
• Check the cabling.
• Consult SEW Service
10
Communication power
section control unit
The inverter coupling does not
support protocol
Replace inverter coupling
11
Communication power
section control unit
Faulty communication with in-
verter coupling at power-up
(CRC fault)
Replace inverter coupling
12
Communication power
section control unit
Inverter coupling uses protocol
that does not match control unit
Replace inverter coupling
13
Communication power
section control unit
Faulty communication with in-
verter coupling during opera-
tion: more than 1 CRC fault per
second
Replace inverter coupling
196
Power sec-
tion
Immediate
stop
14
Control unit configuration
Missing PLD functionality for
EEPROM data set size 7
Replace control unit
15
Inverter coupling fault
Inverter coupling processor has
signaled internal fault
• Consult SEW Service if the
fault occurs again.
• Replace inverter coupling
16
Inverter coupling fault:
PLD version incompatible
Replace inverter coupling
17
Precharge/discharge con-
trol fault
Precharge/discharge control
processor has signaled internal
fault
• Consult SEW Service if the
fault occurs again.
• Replace precharge/dis-
charge controller
18
Defective DC link fan
Faulty DC link fan
• Consult SEW Service
• Check whether DC link
choke fan is connected or
faulty
19
Communication power
section control unit
Faulty communication with in-
verter coupling during opera-
tion: more than 1 internal fault
per second
• Consult SEW Service if the
fault occurs again.
• Replace inverter coupling
20
Communication power
section control unit
The control unit has not sent
any messages to the inverter
coupling for a while
• Consult SEW Service if the
fault occurs again.
• Replace inverter coupling
21
Uz measurement not
plausible
Phase R
Defective phase module
Consult SEW Service if the
fault occurs again.
22
Ur measurement not
plausible
Phase S
23
Uz measurement not
plausible
Phase T
24770531/EN – 11/2017