7
Project planning and startup with MOVITOOLS
®
MotionStudio
Startup of the fieldbus at the DHR21B/41B controller
Manual – DHE/DHF/DHR21B (standard) and DHE/DHF/DHR41B (advanced)
58
7.5.3
Setting the IP address parameters via DCP
Initial startup
For PROFINET IO, the IP address parameters are determined via the "DCP" protocol
(
D
iscovery and
C
onfiguration
P
rotocol). DCP operates with device names. The device
name uniquely identifies a PROFINET IO node in the network. It is identified with the
PROFINET IO controller during the configuration of the node and also set using the
configuration software on the PROFINET IO device. With the aid of the device name,
the controller identifies the device during startup and transfers the corresponding IP
address parameters. Settings directly on the slave are no longer required.
Resetting IP address parameters
If you do not know the IP address parameters and cannot access the inverter using
the serial interface or the DBG60B keypad, you can reset the IP address parameters
to the default values using DIP switch 2
0
.
This action resets the DHR21B/41B option card to the following default values:
•
IP address: 192.168.10.4
•
Subnet mask: 255.255.255.0
•
Standard gateway: 1.0.0.0
•
PROFINET device name: PNETDeviceName_MACID
Proceed as follows:
1. Switch off the 24 V DC supply voltage and the mains voltage.
2. On the DHR21B/41B option card, set DIP switch 2
0
to "1" (= right = ON).
3. Switch the DC 24 V supply voltage and the mains voltage back on.
4. Wait until the DHR21B/41B option card has booted up. This is indicated by the
green "RUN" LED.
ð
The IP address parameters are reset.
ð
You can now access the inverter via the IP address 192.168.10.4.
Setting new IP address parameters
Proceed as follows:
1. Start MOVITOOLS
®
MotionStudio.
2. Select the required address parameters.
3. On the DHR21B/41B option card, set DIP switch 2
0
to "0" (= left = OFF).
4. Switch the device off and back on again.
ð
The new IP address parameters are set.
7.5.4
Setting the IP address parameters
INFORMATION
•
DHCP remains disabled when you reset the DIP switch 2
0
to "0" (= left = OFF).
You can re-activate DHCP via the EtherNet/IP
TM
TCP/IP interface object, para-
meter P785 or the DHCP server by Rockwell Automation.
•
DHCP remains active when resetting the values to the default setting (
P802 Fact-
ory setting
).
22900055/EN – 08/2016