Severn Trent VAX4600 Series Скачать руководство пользователя страница 18

115.6001.10

- 18 -

3.3.2

Abnormally High Chemical Supply Pressure

CAUTION:

 Vaporizer performance will be restricted if ton containers and tank cars produce

abnormally high liquid pressure. Normal ton container pressure ranges (unpadded) are 85-100 psig
(586-690 kPa). Liquid pressure in a padded tank car is normally 125 psig (862 kPa). Vaporizer
capacity is reduced by padding and very low liquid chemical temperature.

Restricted Performance Example

Assume that the liquid chlorine being fed from the tank car is 60°F (15.6°C) and that the vaporizer
water bath temperature is 180°F (82.2°C). The vapor pressure of the liquid chlorine at 60°F (15.6°C)
is approximately 70 psig without any padding, and the thermal difference through the vaporizer
chamber wall between the heated water and the liquid chlorine will be 120°F (49°C). With this
temperature difference, the vaporizer can transfer heat and thereby vaporize the liquid chlorine to
gaseous chlorine.

The Chlorine Institute Pamphlet #54 permits maximum allowable padding pressure to be 190 psig
(1310 kPa) for  liquid chlorine at 60°F (15.6°C). In this case, the liquid pressure in the vaporizer tank
then becomes 190 psig (1310 kPa), instead of 70 psig (483 kPa), because of the padding.

From the vapor pressure curve of chlorine, a 190 psig (1310 kPa) vapor pressure is equivalent to
120°F (49°C) so that the vaporizer must heat the liquid chlorine to 120°F (49°C) prior to vaporization.
With the vaporizer water bath at 180°F (82.2°C), a 60°F (15.6°C) change in temperature is available
to vaporize the chlorine instead of a change in temperature of 120°F (49°C) without padding. The
increased heat required to raise the liquid chlorine temperature 120°F (49°C) reduces the vaporizer
capacity and superheat.

To reduce abnormally high liquid chlorine pressure induced by heat (ton containers) or induced by
padding pressure (tank cars), operate on the gas phase of the source (top container valve) until the
pressure drops to approximately 70 psig (483 kPa). The chlorinator can operate to its maximum
capacity at 20 psig (138 kPa) gas pressure at the inlet to the vacuum regulator but 40 psig (276 kPa)
is preferred. Padding of a tank car will only be required when the liquid chlorine temperature is below
30°F (-1.1°C), and then only a small amount of padding is required.

If padding is used and pressure is maintained above 80 psig (552 kPa), chlorine liquid carry-over can
occur, and must be prevented for proper performance.

3.3.3

Shutdown

The vaporizer can be shut down using two methods:

Caution: 

Liquid chemical must not remain trapped in the vaporizing chamber when the liquid inlet

shutoff valve and gas discharge valve or process equipment is shut off. If liquid is trapped in the
heated vaporizer, the pressure will rise, causing the rupture disc to burst and the pressure relief valve
to open.

a.

Method A (preferred)

Shut off the container liquid supply inlet valve at the vaporizer while maintaining the water bath
temperature. The remaining liquid will vaporize and discharge to the process.

Note: 

The process equipment must be operating. When the gas pressure gauge indicates the

rapid drop in pressure, all the liquid is vaporized. The manual gas discharge valves and the
process equipment may then be shut off.

b.

Method B

Shut off the manual gas discharge valves to the process while maintaining the water bath
temperature. The pressure buildup in the vaporizing chamber will cause the liquid chemical to
return to its source. Shut down the process equipment, then shut off the container liquid supply
valve at the vaporizer.

After completing Method A or B, residual pressurized chemical gas may still be in the vaporizer
chamber. Before disconnecting any pipes, open the manual vent valve to make sure all gas is
vented.

Содержание VAX4600 Series

Страница 1: ...1 115 6001 10 Instruction Manual Vaporizer for Chlorine or Sulfur Dioxide Series VAX4600 CAPITAL CONTROLS...

Страница 2: ...on to instruction operating manuals all instructions given on labels or attached tags should be followed Regardless of these efforts it is not possible to eliminate all hazards from the equipment or f...

Страница 3: ...off Switch 23 4 6 Water Temperature Control Thermostat 23 4 7 High and Low Water TemperatureAlarm Switches 23 4 8 Cathodic Protection Anode Replacement 23 4 9 Recommended Torque Values 25 5 TROUBLESHO...

Страница 4: ...115 6001 10 4...

Страница 5: ...n The unit consists of a hot water tank a chemical vaporizing chamber a NEMA 4X heater control circuit a NEMA 4X water level control circuit chemical and hot water monitoring instruments cathodic prot...

Страница 6: ...115 6001 10 6 Figure 1 Vaporizer Flow Diagram Figure 2 Chemical Boiling Points at System Pressure...

Страница 7: ...o water condition The water level control switch is field wired to a solenoid valve in the water supply line providing automatic water level control The low water level alarm switch may be field wired...

Страница 8: ...tion chamber is manufactured from 6 ASTM SA 53 B seamless carbon steel pipe All welds are in accordance with ASME boiler and pressured vessel codes Section VIII Division I Both inlet and outlet connec...

Страница 9: ...9 115 6001 10 Figure 4 Cabinet Dimensions Utility Connection Locations...

Страница 10: ...rsibly Prolonged operation under conditions of RF interference though not unsafe may damage some instrument components and is not recommended 1 4 Principle of Operation Liquid is transferred from its...

Страница 11: ...ension requirements 2 2 Mounting Install the vaporizer on a mounting pad of concrete or other suitable material approximately 2 50 mm high Secure using 3 8 diameter bolts See Figure 4 for mounting hol...

Страница 12: ...115 6001 10 12 Figure 6 Vaporizer Piping Connections...

Страница 13: ...al gas liquid lines and water lines as shown in Figure 6 Plumbing must be in accordance with local codes When installing the nipples tees and 1 ammonia unions into the inlet and outlet ports of the ch...

Страница 14: ...ve on the free end of the flexible connector and connect to the liquid valve of the chemical container 2 3 3 Water Line Connections See Figure 6 a Install 1 overflow piping to the outlet provided on t...

Страница 15: ...e control circuit terminal block d Wire the water fill solenoid valve to the control circuit terminal block Do not apply power 2 4 3 Alarm Switches a The low water temperature alarm switch can be conn...

Страница 16: ...ncy procedures Before continuing with the startup contact Capital Controls with questions or to arrange a training program if necessary 3 3 1 Start Up a Turn on the power to the heaters control circui...

Страница 17: ...17 115 6001 10 Figure 8 Chlorine and Sulfur Dioxide Vaporizer Components...

Страница 18: ...ine pressure induced by heat ton containers or induced by padding pressure tank cars operate on the gas phase of the source top container valve until the pressure drops to approximately 70 psig 483 kP...

Страница 19: ...the instrument panel ammeter This should be read and adjusted weekly using the potentiometer knob directly below the ammeter A zero reading at all potentiometer settings indicates replacement of anod...

Страница 20: ...zero and leave open 4 Disconnect the 1 union in the chemical liquid pipe at the vaporizer after the chemical liquid valve f Pass dry air into the vaporizer through the chemical liquid inlet at the di...

Страница 21: ...reducing valve be disassembled and cleaned Refer to the manufacturer s instructions 1 Loosen fasteners housing the strainer or cartridge 2 Wash the strainer in hot soapy water discard the cartridge 3...

Страница 22: ...ches Refer to Figures 3 and 4 If any of the final control elements are not functioning properly the cause may be a malfunctioning water level switch or water temperature control switch Refer to the wi...

Страница 23: ...82 C Low Temperature Alarm Switch 170 F 77 C High Temperature Alarm Switch 190 F 88 C 4 8 Cathodic Protection Anode Replacement The water wetted surfaces of the vaporizer are protected against corrosi...

Страница 24: ...115 6001 10 24 Figure 10 Replacing Heater Element...

Страница 25: ...a W 4 n e p o e v l a v l l i f l a u n a M a h c t i w s l o r t n o c l e v e l r e t a W b y l n o l l i f c i t a m o t u a g n i n o i t c n u f l a m t o n d i o n e l o s e v l a v l l i f c i...

Страница 26: ...115 6001 10 26...

Страница 27: ...27 115 6001 10...

Страница 28: ...e 05 06 CAPITAL CONTROLS Severn Trent Services 3000 Advance Lane Colmar PA 18915 Tel 215 997 4000 Fax 215 997 4062 Web www severntrentservices com E mail marketing severntrentservices com UNITEDKINGDO...

Отзывы: