42
SETRONIC Verona
P RO BLEM
C HEC K
Control unit does not turn on
The polarity of the cables
Power tension
That the terminals are correctly inserted
The detector unit does not turn on
As indicated above
That the RJ45 plug is correctly inserted
The yellow and green LEDs on the
detector flash every 2 seconds and the
control unit shows "C-Err"
The polarity of the serial cable (as
between A and B)
On switching on the system, the control
unit displays “C-Err” and the red alarm
LED stays on as does the yellow trouble
LED
The polarity of the serial cable (A and B
inversion)
Maintenance request signal
Cleaning of the front of the detector
The presence of vapour, fog or dust in the
environment
Check the correct alignment
Sporadic fault signals
RX Adjustment value, as necessary bring
back to 100%
The rigidity of the structure to which the
detector is fastened
The presence of moveable obstacles that
intercept the beam
That the air is clean as compared with
when the calibration was carried out, with
consequent oversignal.
E
N
G
L
IS
H