32
SETRONIC Verona
< Sensibility >
Go into the set-up menu as explained on page 30 and
select “Sensibility”
Detec: 0
Smoke: 673
Loading Data
From Detector
Wait a couple of seconds for the control unit to read
the detector data.
Observe the interference values (DETEC) for at least a couple of minutes
and set the threshold for a figure above the highest peak read.
NOTE: The following possible threshold values can be selected: 200, 284, 371, 461, 581,
673, 752, 825, 914, 984, 1066, 1137, 1219, 1280, 1383, 1462. With threshold values between
200 and 581 it will say “warn” as the detector becomes very sensitive, as well as the
minimum range required by the regulations.
P RE S S
OK
W A I T F OR 2 S E C ON D S ,
T H E N P RE S S
OK
8.2 REGULATION OF SENSITIVITY THRESHOLD
Th e s en si ti vi ty th re sh o ld f or s mok e an d fi r e mu st b e ad ju st ed
acc ord in g to th e b ac k grou n d e n vir on m en ta l in t er f er en c e at th e
in stal la tion s it e.
U sin g th e “S en s ib i lity ” m en u y o u s ee a n u m er i cal r ead ou t for th e
in t er f er en c e an d s o a s u itab le ma rg in c an b e u s ed to en su r e th i s
d oe s n ot ex c e ed th e t h r e sh o ld an d ca u s e fa l s e a lar m s.
In the first line the interference figure is shown in
real time.
The second line shows the smoke threshold, with
default of 673. With the keys
it is possible to
increase or reduce this value.
E
N
G
L
IS
H
Содержание ILIA-OZ
Страница 1: ...SETRONIC Verona 1 ...