HOLDING REGISTERS
Data type
Description
Data
Default
Values
55
Analogue output type (Ao1)
unsigned int.
Disables or selects the analogue output
type for Ao1
0—5
1
0 =
1 =
2 =
3 =
4 =
5 =
Not in use
0—10 VDC
2—10 VDC
0—20 mA
4—20 mA
PWM
56
Analogue output function
(Ao1)
unsigned int.
Sets the output function for Ao1
0—2
0
0 =
1 =
2 =
Linear
Control
PID
57
Analogue output mode (Ao1)
unsigned int.
Analogue output mode: Cool
(0—10 VDC) / Heat (10—0 VDC)
0—1
0
0 =
Cool
0—10 VDC (2—10 VDC)
0—20 mA (4—20 mA)
0—100 %
1 =
Heat
10—0 VDC (10—2 VDC)
20—0 mA (20—4 mA)
100—0 %
58
Minimum value of the
analogue output (Ao1)
unsigned int.
Minimum value of the analogue output
Ao1, calculated from the control range
of the normally assigned input, in
percentages
0—40
0
0 =
40 =
0 %
40 %
59
Maximum value of the
analogue output (Ao1)
unsigned int.
Maximum value of the analogue output
Ao1, calculated from the control range
of the normally assigned input, in
percentages
60—100
100
60 =
100 =
60 %
100 %
60
Assign normal input to
analogue output (Ao1)
unsigned int.
Assigns normal analogue or temperature
input to analogue output Ao1
0—3
0
0 =
1 =
2 =
3 =
T1
T2
Ai1
Ai2
61
Assign high priority input to
analogue output (Ao1)
unsigned int.
Assigns high priority analogue or
temperature input to analogue output
Ao1.
Active only if controlled output is
selected.
0—3
2
0 =
1 =
2 =
3 =
T1
T2
Ai1
Ai2
62
Time to maximum output
(Ao1)
unsigned int.
Time for the output to rise to maximum
value.
Active only if control function is
selected.
0—100 s
60 s
60 =
60 s
63
Kp value (Ao1)
unsigned int.
Proportional gain value for Ao1.
Active only if a PID function is selected.
1—1.000
10
10 =
1,0 gain
64
Ti value (Ao1)
unsigned int.
Integration period value for Ao1.
Active only if a PID function is selected.
1—6.000
100
1 =
100 =
0,1 s
10 s
65
Td value (Ao1)
unsigned int.
Derivative period value for Ao1.
Active only if a PID function is selected.
0—6.000
10
0 =
10 =
0 s
1 s
66
Analogue output (Ao2)
relation to
(Ao1)
unsigned int.
Sets the relation between analogue
output Ao1 and analogue output Ao2
0—2
0
0 =
1 =
2 =
Free (without relation)
Balanced
Unbalanced
67
Unbalanced coefficient (Ao2)
signed int.
Difference between analogue output Ao1
and analogue output Ao2 in percents.
Active only in unbalanced mode.
-200—200
0
200 =
20 %
68
Analogue output type (Ao2)
unsigned int.
Disables or selects the analogue output
type for Ao2
0—5
1
0 =
1 =
2 =
3 =
4 =
5 =
Not in use
0—10 VDC
2—10 VDC
0—20 mA
4—20 mA
PWM
69
Analogue output function
(Ao2)
unsigned int.
Sets the output function for Ao2.
Active
only if not in relation.
0—2
0
0 =
1 =
2 =
Linear
Control
PID
70
Analogue output mode (Ao2) unsigned int.
Analogue output mode: Cool (0—10 VDC)
/ Heat (10—0 VDC)
0—1
0
0 =
Cool
0—10 VDC (2—10 VDC)
0—20 mA (4—20 mA)
0—100 %
1 =
Heat
10—0 VDC (10—2 VDC)
20—0 mA (20—4 mA)
100—0 %
78
Td value (Ao2)
unsigned int.
Derivative period value for Ao2.
Active only if a PID function is selected.
0—6.000
10
0 =
10 =
0 s
1 s
71
Minimum value of the
analogue output (Ao2)
unsigned int.
Minimum value of the analogue output
Ao2, calculated from the control range
of the normally assigned input, in
percentages
0—40
0
0 =
40 =
0 %
40 %
72
Maximum value of the
analogue output (Ao2)
unsigned int.
Maximum value of the analogue output
Ao2, calculated from the control range
of the normally assigned input, in
percentages
60—100
100
60 =
100 =
60 %
100 %
73
Assign normal input to
analogue output (Ao2)
unsigned int.
Assigns normal analogue or temperature
input to analogue output Ao2.
Active
only if not in relation.
0—3
0
0 =
1 =
2 =
3 =
T1
T2
Ai1
Ai2