www.sentera.eu
MIW-MCS-1-LCD-EN-000 - 20 / 07 / 2016
29 - 33
INPUT REGISTERS
Data type
Description
Data
Values
35
Off level for analogue input (Ai1)
unsigned int.
Selected off level for analogue input (Ai1)
0—950
300 =
300 =
3,0 VDC (30 %)
6 mA (30 %)
36
Setpoint for analogue input (Ai1)
unsigned int.
Selected setpoint for analogue input (Ai1)
200—1.000
300 =
300 =
3,0 VDC (30 %)
6 mA (30 %)
37
Hysteresis for analogue input (Ai1)
unsigned int.
Selected hysteresis for analogue input (Ai1)
50, 100,
150, 200
50 =
100 =
150 =
200 =
0,5 VDC = 1 mA (0,5 %)
1,0 VDC = 2 mA (10 %)
1,5 VDC = 3 mA (15 %)
2,0 VDC = 4 mA (20 %)
38
Reserved, returns 0
39
Analogue input sensor range (Ai2)
unsigned int.
Selected analogue input sensor range (Ai2),
calculated from holding registers values
0—1.000
0—1.000
0—10 VDC
40
Analogue input control range (Ai2)
unsigned int.
Selected analogue input control range (Ai2),
calculated from holding registers values
0—1.000
0—1.000
0—10 VDC
41
Off level for analogue input (Ai2)
unsigned int.
Selected off level for analogue input (Ai2)
0—950
300 =
300 =
3,0 VDC (30 %)
6 mA (30 %)
42
Setpoint for analogue input (Ai2)
unsigned int.
Selected setpoint for analogue input (Ai2)
200—1.000
300 =
300 =
3,0 VDC (30 %)
6 mA (30 %)
43
Hysteresis for analogue input (Ai2)
unsigned int.
Selected hysteresis for analogue input (Ai2)
50, 100,
150, 200
50 =
100 =
150 =
200 =
0,5 VDC = 1 mA (0,5 %)
1,0 VDC = 2 mA (10 %)
1,5 VDC = 3 mA (15 %)
2,0 VDC = 4 mA (20 %)
44-46
Reserved, returns 0
HOLDING REGISTERS
Data type
Description
Data
Default
Values
1
Device slave address
unsigned int.
Modbus device address
1—247
1
2
Modbus baud rate
unsigned int.
Modbus communication baud rate
1—4
2
1 =
2 =
3 =
4 =
9.600
19.200
38.400
57.600
3
Modbus parity
unsigned int.
Parity check mode
0—2
1
0 =
1 =
2 =
8N1
8E1
8O1
4
Device type
unsigned int.
Device type (Read only)
MCS-1-LCD = 2003
5
HW version
unsigned int.
Hardware version of the device (Read
only)
XXXX
0 x 0160 =
HW version 1.60
6
FW version
unsigned int.
Firmware version of the device (Read
only)
XXXX
0 x 0120 =
FW version 1.20
7
Operating mode
unsigned int.
Enables Modbus control and disables the
jumpers
0—1
0
0 =
1 =
Standalone mode
Modbus mode
8
Output override
unsigned int.
Enables the direct control over the
outputs.
Always settable. Active only if
holding register 7 is set to 1.
0—1
0
0 =
1 =
Disabled
Enabled
9
Device functionality
unsigned int.
Selects the operational mode
0—8
0
0 =
Temperature cool
1 =
Temperature heat
2 =
Relative humidity
3 =
CO
2
4 =
Air quality
5 =
Differential pressure
6 =
Temperature and CO
2
7 =
Differential pressure and
temperature
8 =
Free
11
Temperature input state (T1)
unsigned int.
Enables or disables the temperature input
(T1)
0—1
1
0 =
1 =
Not in use
In use
14
Minimum control range (T1)
signed int.
Minimum control range value for T1
-300—700
0
0 =
0 °C
15
Maximum control range (T1)
signed int.
Maximum control range value for T1
-300—700
400
400 =
40 °C
16
Off level for temperature
input (T1)
signed int.
Off level for temperature input T1
-200—600
-100
-100 =
-10 °C
17
Setpoint for temperature
input (T1)
signed int.
Setpoint for temperature input T1.
Used
only if assigned to a controlled analogue
output, PID or relay output.
-200—600
200
200 =
20 °C
18
Hysteresis for temperature
input (T1)
signed int.
Hysteresis for temperature input T1
.
Used only if assigned to controlled
analogue output.
5, 10, 15, 20,
25, 30
20
20 =
2,0 °C
19
Calibration of temperature
input (T1)
unsigned int.
Start or reset factory calibration of
temperature input T1
0—2
0
0 =
1 =
2 =
Stand-by
Start user calibration
Reset factory calibration
20
Temperature input state (T2)
unsigned int.
Enables or disables the temperature input
(T2)
0—1
1
0 =
1 =
Not in use
In use
23
Minimum control range (T2)
signed int.
Minimum control range value for T2
-300—700
0
0 =
0 °C
24
Maximum control range (T2)
signed int.
Maximum control range value for T2
-300—700
400
400 =
40 °C
25
Off level for temperature
input (T2)
signed int.
Off level for temperature input T2
-200—600
-100
-100 =
-10 °C
26
Setpoint for temperature
input (T2)
signed int.
Setpoint for temperature input T2.
Used
only if assigned to a controlled analogue
output, PID or relay output.
-200—600
200
200 =
20 °C
MCS-1-LCD
MULTIFUNCTIONAL LOGIC