HOLDING REGISTERS
Data type
Description
Data
Default
Values
27
Hysteresis for temperature
input (T2)
signed int.
Hysteresis for temperature input T2
.
Used only if assigned to controlled
analogue output.
5, 10, 15, 20,
25, 30
20
20 =
2,0 °C
28
Calibration of temperature
input (T2)
unsigned int.
Start or reset factory calibration of
temperature input T2
0—2
0
0 =
1 =
2 =
Stand-by
Start user calibration
Reset factory calibration
29
Analogue input type (Ai1)
unsigned int.
Disables or selects the analogue input
type for Ai1
0—5
1
0 =
1 =
2 =
3 =
4 =
5 =
Not in use
0—10 VDC
2—10 VDC
0— 20 mA
4—20 mA
PWM
32
Minimum control range (Ai1)
signed int.
Minimum control range value for Ai1
0—1.000
0
300 =
3,0 VDC = 6,0 mA (30 %)
33
Maximum control range (Ai1)
signed int.
Maximum control range value for Ai1
0—1.000
1.000
1.000 =
10,0 VDC = 20,0 mA (100 %)
34
Off level for analogue input
(Ai1)
signed int.
Off level for analogue input Ai1
0—950
0
300 =
3,0 VDC = 6,0 mA (30 %)
35
Setpoint for analogue input
(Ai1)
signed int.
Setpoint for analogue input Ai1.
Used only
if assigned to controlled analogue output,
PID or relay output.
200—1.000
500
500 =
5,0 VDC = 10,0 mA (50 %)
36
Hysteresis for analogue input
(Ai1)
signed int.
Hysteresis for analogue input Ai1.
Used
only if assigned to controlled analogue
output.
50, 100, 150, 200
100
100 =
1,0 VDC = 2,0 mA (10 %)
37
Reserved, returns 0
38
Analogue input type (Ai2)
unsigned int.
Disables or selects the analogue input
type for Ai2
0—5
1
0 =
1 =
2 =
3 =
4 =
5 =
Not in use
0—10 VDC
2—10 VDC
0— 20 mA
4—20 mA
PWM
41
Minimum control range (Ai2)
signed int.
Minimum control range value for Ai2
0—1.000
0
300 =
3,0 VDC = 6,0 mA (30 %)
42
Maximum control range (Ai2)
signed int.
Maximum control range value for Ai2
0—1.000
1.000
1.000 =
10,0 VDC = 20,0 mA (100 %)
43
Off level for analogue input
(Ai2)
signed int.
Off level for analogue input Ai2
0—950
0
300 =
3,0 VDC = 6,0 mA (30 %)
44
Setpoint for analogue input
(Ai2)
signed int.
Setpoint for analogue input Ai2.
Used
only if assigned to controlled analogue
output, PID or relay output.
200—1.000
500
500 =
5,0 VDC = 10,0 mA (50 %)
45
Hysteresis for analogue input
(Ai2)
signed int.
Hysteresis for analogue input Ai2.
Used
only if assigned to controlled analogue
output.
50, 100, 150, 200
100
100 =
1,0 VDC = 2,0 mA (10 %)
46
Reserved, returns 0
47
Digital input function (Di1)
unsigned int.
Disables or selects a digital input function
for Di1
0—7
0
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
Not in use
Remote off for Ao1
Maximum output for Ao1
Mode selection Ao1
Remote off for Ao2
Maximum output for Ao2
Mode selection Ao2
Relay control
48
Digital input active state (Di1)
unsigned int.
Selects active state for digital input Di1
0—1
0
0 =
1 =
High
Low
49
Digital input function (Di2)
unsigned int.
Disables or selects a digital input
function for Di2
0—7
0
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
Not in use
Remote off for Ao1
Maximum output for Ao1
Mode selection Ao1
Remote off for Ao2
Maximum output for Ao2
Mode selection Ao2
Relay control
50
Digital input active state
(Di2)
unsigned int.
Selects active state for digital input Di2
0—1
0
0 =
1 =
High
Low
51
Digital input function (Di3)
unsigned int.
Disables or selects a digital input
function for Di3
0—7
0
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
Not in use
Remote off for Ao1
Maximum output for Ao1
Mode selection Ao1
Remote off for Ao2
Maximum output for Ao2
Mode selection Ao2
Relay control
52
Digital input active state
(Di3)
unsigned int.
Selects active state for digital input Di3
0—1
0
0 =
1 =
High
Low
53
Digital input function (Di4)
unsigned int.
Disables or selects a digital input
function for Di4
0—7
0
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
Not in use
Remote off for Ao1
Maximum output for Ao1
Mode selection Ao1
Remote off for Ao2
Maximum output for Ao2
Mode selection Ao2
Relay control
54
Digital input active state
(Di4)
unsigned int.
Selects active state for digital input Di4
0—1
0
0 =
1 =
High
Low
MCS-1-LCD