Appendix A – Specifi cations
Models
MS2000/12
MS2812
MS2024
MS4024
MS4048
MS2012 (-15/-20B)
MS4048-20B
Inverter Specifi cations
Input battery voltage range
9.0 to 16.8 VDC
18.0 to 33.6 VDC
36.0 to 67.6 VDC
Absolute maximum DC input
25 VDC
35 VDC
AC output voltage accuracy
120 VAC ±5% (≤ continuous power)
Output frequency and accuracy
60 Hz ± 0.1 Hz
Total Harmonic Distortion (THD)
< 5%
Continuous power output (at 25°C)
2000 VA
2800 VA
2000 VA
4000 VA
4000 VA
Continuous AC output current
17 A
23 A
17 A
33 A
1 msec surge current (amps AC)
50
70
75
120
100 msec surge current (amps AC)
33
40
37
82
72
5 sec surge power (real watts)
3300
3900
2850
5800
8500
30 sec surge power (real watts)
3100
3800
2750
5400
5750
5 min surge power (real watts)
2800
3200
2700
4900
5250
30 min surge power (real watts)
2200
3000
2200
4500
4750
Maximum continuous input current
267 ADC
373 ADC
133 ADC
267 ADC
133 ADC
Inverter effi
ciency (peak)
90.6%
90%
86%
93.7%
94.0%
HBCO/HBCI (High Battery Cut Out/In)
16.8/16.5 VDC
33.6/33.0 VDC
67.6/66.7 VDC
LBCO/LBCI (Low Battery Cut Out/In)
9.0 (adj)/12.5 VDC
18.0 (adj)/25.0 VDC
36.0 (adj)/50.0 VDC
AC Relay transfer time (minimum)
16 msec
Power consumption – searching
<8 watts
Power consumption – inverting (no load)
25 watts
30 watts
25 watts
Output waveform
Pure Sine Wave
Charger Specifi cations
Continuous charger output at 25°C
100 ADC
125 ADC
60 ADC
105 ADC
60 ADC
Input current for continuous rated output
15 AAC
18 AAC
7.9 AAC
29 AAC
30 AAC
Charger effi
ciency
85%
AC input range (frequency/voltage)
50 to 70 Hz/ 60 to 140 VAC (120 VAC nominal)
Power factor
> 0.95
General Features and Capabilities
Transfer relay capability
30AAC max. each input (30AAC total on MS2000 models, 60AAC total on all other models)
**
Five-stage charging capability
Bulk, Absorb, Float, Equalize (requires remote), and Battery Saver™
Battery temperature compensation
Standard with available temp sensor connected (battery temp 0 – 50°C)
Internal cooling
0 to 120 cfm variable speed drive using dual 92 mm brushless DC fan
Overcurrent protection
with two overlapping circuits
Over-temperature protection
on transformer, MOSFETS, and battery
Corrosion protection
PCB’s conformal coated, powder coated chassis/top, and stainless steel fasteners
Safety listings
ETL listed to UL/cUL 458, UL 1741, CSA C22.2 No. 107.1-01, and meets KKK-A-1822E std.
***
Warranty
3 years parts and labor
Branch-rated output circuit breakers
Optional on MS2000 (15 or 20 amp breakers) or MS2012 (15 or 20 amp breakers)
Environmental Specifi cations
Temperature (Operating/Non-operating)
-20°C to +60°C (-4°F to 140°F)/-40°C to +70°C (-40°F to 158°F)
Operating humidity
0 to 95% RH non-condensing
Physical Specifi cations
Unit dimensions (length x width x height)
13.75” x 12.65” x 8.0” (34.9 cm x 32.1 cm x 20.3 cm) [Height on MS2000 models is 7.0”/17.8 cm]
Shipping dimensions (L x W x H)
19” x 17” x 13” (48.3 cm x 43.2 cm x 33 cm)
Mounting
Shelf or wall (vents not allowed to face downward unless ME-CB or MMP/MP is installed)
Unit weight
42 lb (19.1 kg)
55 lb (24.9 kg)
41 lb (18.6 kg)
55 lb (24.9 kg)
55 lb (24.9 kg)
Shipping weight
48 lb (21.8 kg)
62 lb (28.1 kg)
49 lb (22.2 kg)
62 lb (28.1 kg)
62 lb (28.1 kg)
Max operating altitude
15,000’ (4570 m)
** The pass-thru capability on each leg of the – 15B and – 20B models is limited by the output breaker size on each output.
*** MS2000 models
ETL listed to UL/cUL 458, CSA C22.2 No. 107.1-01, and meet KKK-A-1822E standard.
Specifi cations @ 25°C – Subject to change without notice.
Appendix A – Specifi cations and Optional Equipment
A-1 Inverter/Charger Specifi cations
Содержание Magnum Energy MS Series
Страница 1: ...Pure Sine Wave Inverter Charger MS Series Owner s Manual...
Страница 22: ...Page 12 2016 Sensata Technologies Installation Figure 2 4 MS Dimensions MS2012 MS2812 MS2024 MS4024 MS4048...
Страница 23: ...2016 Sensata Technologies Page 13 Installation Figure 2 5 MS Dimensions MS2000...
Страница 26: ...Page 16 2016 Sensata Technologies Installation Figure 2 6 DC and Battery Temperature Sensor Wiring...
Страница 38: ...Page 28 2016 Sensata Technologies Installation Figure 2 13 AC Wiring for Single In Dual Out Con gurations...
Страница 39: ...2016 Sensata Technologies Page 29 Installation Figure 2 14 AC Wiring for Dual In Single Out Con gurations...
Страница 40: ...Page 30 2016 Sensata Technologies Installation Figure 2 15 AC Wiring for Dual In Dual Out Con gurations...
Страница 43: ...2016 Sensata Technologies Page 33 Installation Figure 2 16 AC Wiring for MS2000 Models...
Страница 44: ...Page 34 2016 Sensata Technologies Installation Figure 2 17 AC Wiring for MS2000 15B 20B Models...