Page 37
Installation
Method 3 (Figure 2-21):
The AC grounding electrode conductor (GEC – AC) is bonded to the
DC ground point and the DC grounding electrode conductor (GEC – DC) is the
only connection
to
the grounding electrode, which must be a rod, pipe, or plate electrode.
In this method, since there is only one connection to the ground rod, the DC grounding electrode
conductor is not required to be larger than #6 AWG (13 mm
2
) copper. The reasoning for allowing
this smaller grounding electrode conductor is that it is only required to stabilize the system voltage
with respect to earth, and the other properly-sized conductors in each electrical system will safely
carry any fault currents if they occur.
Method 2 (Figure 2-20):
When the AC and DC service panels are near each other, then the AC
grounding electrode conductor (GEC – AC) and DC grounding electrode conductor (GEC – DC) can
be connected to a single grounding electrode. In this method—since there are multiple connections
to the DC grounding electrode (GEC – DC)—the size of the DC grounding electrode conductor cannot
be smaller than the largest conductor in the DC system (usually the battery-to-inverter cable).
Figure 2-20, Multiple Connections to DC Ground Rod (Method 2)
Figure 2-21, Single Connection to DC Ground Rod (Method 3)
AC
DC Service
Panel
AC Service
Panel
DC Electrical System
AC Electrical System
Neutral
Positive
Negative
DC
Grounding
System
Negative
SBJ
GC
GE
GEC-AC
EGC - AC
AC Ground
DC Ground
SBJ
EGC - DC
GC
Neutral
Hot
GEC-DC
GBB
GBB
Grounding Electrode
(AC and DC sides shared)
MS Series Inverter/Charger
AC
DC Service
Panel
AC Service
Panel
DC Electrical System
AC Electrical System
Neutral
Positive
Negative
DC
Grounding
System
Negative
SBJ
GC
GEC-AC
EGC - AC
AC Ground
DC Ground
SBJ
EGC - DC
GC
Neutral
Hot
GEC-DC
GE
GBB
GBB
Grounding Electrode
(DC side dedicated)
MS Series Inverter/Charger
Содержание Magnum Energy MS Series
Страница 1: ...Pure Sine Wave Inverter Charger MS Series Owner s Manual...
Страница 22: ...Page 12 2016 Sensata Technologies Installation Figure 2 4 MS Dimensions MS2012 MS2812 MS2024 MS4024 MS4048...
Страница 23: ...2016 Sensata Technologies Page 13 Installation Figure 2 5 MS Dimensions MS2000...
Страница 26: ...Page 16 2016 Sensata Technologies Installation Figure 2 6 DC and Battery Temperature Sensor Wiring...
Страница 38: ...Page 28 2016 Sensata Technologies Installation Figure 2 13 AC Wiring for Single In Dual Out Con gurations...
Страница 39: ...2016 Sensata Technologies Page 29 Installation Figure 2 14 AC Wiring for Dual In Single Out Con gurations...
Страница 40: ...Page 30 2016 Sensata Technologies Installation Figure 2 15 AC Wiring for Dual In Dual Out Con gurations...
Страница 43: ...2016 Sensata Technologies Page 33 Installation Figure 2 16 AC Wiring for MS2000 Models...
Страница 44: ...Page 34 2016 Sensata Technologies Installation Figure 2 17 AC Wiring for MS2000 15B 20B Models...