SENS EnerGenius Technical Manual  

16 

Service hotline: 1.800.742.2326 
                           1.303.678.7500  

Red for internal charger failure 

B. FRONT PANEL LED INDICATOR DEFINITIONS AND TROUBLE SHOOTING: 

 

  

*Red for low battery voltage 

*Red for low or missing AC input 

Green for normal voltage (float charge) 

Yellow for boost voltage (fast charge) 

*Red for open, wrong voltage, or reversed battery 

Green for normal AC input 

*Red for excessive battery voltage 

DC Volt/Amp Meter Display 

Green for temperature-corrected charger voltage 

Battery Fault Protection and Alarm: 

The battery charger automatically checks the battery voltage before power-on startup. If the battery voltage is 
either too high or too low, the charger enters a “lockout” period for approximately 10 seconds before attempting 
an automatic restart. 

The “JUMP” feature (described in Section 11-G in this manual) may be used to temporarily allow the battery 
charger to override the lockout and start charging a low-voltage discharged battery – this override should be used 
only up to approximately 5 minutes of recharge time, then the jumper should be replaced in its normal position  

The battery charger will not start if the battery or battery cables have a short circuit, and will start automatically 
with a good battery if the short circuit is removed. 

In addition to detecting low battery voltage and short circuits, the battery charger also monitors the peak voltage 
at its DC output terminals and will enter lockout if the DC cable resistance is too high or if the battery’s internal 
resistance is too high   

If a battery is connected backwards, this reverse polarity condition will keep the battery charger in lockout and it 
will remain in lockout until the battery is disconnected. A reverse polarity condition will not blow a fuse; the bat-
tery charger will start and run normally when a good battery is connected with correct polarity.   

Whenever one of these fault conditions triggers the battery fault protection circuitry as described above, the 
“Batt Fault” relay and LED are both activated.  

Robust Hardened Construction: 

Shock and Vibration tested to UL 991, 2G. 

Shock and Vibration tested to UL 991, 5G option available. 

Lightning transient immunity to ANSI/IEEE C62.41 Cat. B and EN 50082-2 heavy industrial. 

Wide operating temperature range: -20 to + 40 Degrees C. Charger will operate at reduced output current rating 
up to +60 Degrees C. 

Conformal coated printed wiring boards for erosion protection. 

Worl dw ide  Agency  App rovals: 

UL listed, UL 1012, UL 1236. 

CUL listed to CSA C22.2 107.2- M89. 

CE marked for EMC directive (industrial environment) and EN 60335-2-29. 

Worldwide operating voltage and frequency ranges. 

* Active only on five alarm models - see page 3 for model number breakdown 

Содержание EnerGenius NRG22-10

Страница 1: ...y Charger SENS Part Number Document Revision DCN Number Date 101295 L 105749 July 28 2009 Installation or service questions Call SENS at 1 800 742 2326 303 678 7500 between 8 a m and 5 p m Mountain Ti...

Страница 2: ...gs on these products and on the engine A Someone should be within range of your voice or close enough to come to your aid when you work near a storage battery B Have plenty of fresh water and soap nea...

Страница 3: ...ber Breakout NRG 22 10 Model Output Output Input Voltage Alarm System Agency Category Voltage Current Frequency Code 12 12 volts 10 10 Amps H 120 208 240V C 5 Alarms L UL S Standard 24 24 volts 50 60...

Страница 4: ...WITH LOCAL ELECTRICAL CODES AND OTHER APPLICABLE INSTALLATION CODES B INSTALLATION MUST BE MADE ACCORDING TO THE INSTALLATION INSTRUCTIONS AND ALL APPLICABLE SAFETY REGULATIONS WARNING ONLY TRAINED A...

Страница 5: ...ected for service remove the output wiring in the reverse of the order given above D Be sure battery terminals are clean and properly tightened Be careful to keep corrosion from coming in contact with...

Страница 6: ...or battery owner s manual and make sure that the 12V 24V select jumper is set to the correct voltage 2 CHARGER LOCATION Do not set a battery or any other object on top of the charger This will obstru...

Страница 7: ...erconnects The above lengths are for operation at 25C For high temperature installations 40C reduce lengths by 10 In the case of high resistance in the cables to the battery the charger may cycle betw...

Страница 8: ...rger by the chassis only Remove the cover only when access is essential for installation and service and replace it promptly when finished B If possible wear an approved static protection strap If one...

Страница 9: ...nch pounds 10 WIRING A All wiring must comply with applicable codes and local ordinances See Section 5 for recommended gauges B The charger contains a DC output fuse for internal fault protection but...

Страница 10: ...KDOWN FIGURE 2A FIGURE 2B E Connect the AC line and neutral conductors at TB1 If there is an identified grounded circuit con ductor neutral attach it to the terminal marked N TB1 will accept 14 6 AWG...

Страница 11: ...K with no AC input TB5 6 FAIL Defaults to Fail with no AC input TB5 9 FAIL Defaults to OK with no AC input TB5 12 FAIL Defaults to OK with no battery TB5 15 FAIL Defaults to fail with no battery RELAY...

Страница 12: ...e 230V position for nominal mains voltages between 208V and 240V B Set the battery range jumper JP1A according to nominal battery voltage Use the 12V position for 12V batteries Use the 24V position fo...

Страница 13: ...SERVICE CONSULT THE BATTERY MANUFACTURER TO DETERMINE IF AND HOW THEY CAN BE SAFELY RESTORED TO SERVICE WARNING NEVER LEAVE A JUMPER IN THE JUMP POSITION DURING NORMAL OPERATION THIS DISABLES THE BATT...

Страница 14: ...onnect AC power then correct the jumper setting or battery voltage before proceeding E After a short delay typically 10 seconds or less the charger will produce output F If the meter display jumper is...

Страница 15: ...a ture increases The output voltage is clamped at 0 and 40 Degrees C to protect against extremely high or low output voltage See chart below Fault Tolerant The charger is protected from the following...

Страница 16: ...short circuit is removed In addition to detecting low battery voltage and short circuits the battery charger also monitors the peak voltage at its DC output terminals and will enter lockout if the DC...

Страница 17: ...On if Temperature Com pensation Working Off if Temperature Compen sation Option not used Confirm if temperature compensation is in tended to be used Only one sensor Local or re mote should be connect...

Страница 18: ...anch circuit breaker and any other disconnect devices 2 The meter display should light immediately after power on The green AC ON LED should be lighted If a temperature sensor is present either intern...

Отзывы: