SENS EnerGenius Technical Manual  

Service hotline: 1.800.742.2326 
                           1.303.678.7500  

A. See the safety instructions for important information concerning the charger location. 
B. The charger should be installed in a sheltered area, protected from rain and snow. 
C. The charger should not be located where temperatures are expected to be colder than -20º C, or hotter than +40º 

C for operation at rated output current.                  

 
 
              
                
 
 
D. Allow sufficient room for routing the fixed wiring to the charger. AC input enters the left side; DC output and 

alarms exit on the right. 

E.

Leave clear space for ventilation all around the unit: at least 6 inches (15 cm) at the top and bottom; at least 
2 inches (5 cm) on the sides. 

F.

Charger should be mounted on a flat vertical surface so that the chassis does not warp when tightened to the 
wall.                                                                                                                                                                  

G. The charger should be mounted vertically, with the input and output terminal blocks lowermost.   
              
              
              
              
                
H. Do not mount the charger over any heat generating equipment. 
I.

Minimize vibrations that the charger will be subjected to. 

WARNING: 
OTHER MOUNTING ORIENTATIONS INTERFERE WITH PROPER 
VENTILATION AND MAY CAUSE THE CHARGER TO OVERHEAT. 

8. STATIC DISCHARGE PRECAUTIONS 

       

The printed circuit board contains static sensitive components. Damage can occur even when static levels are too 
low to produce a noticeable discharge shock. To avoid static discharge damage: 

A. Handle the charger by the chassis only. Remove the cover only when access is essential for installation and 

service, and replace it promptly when finished. 

B. If possible, wear an approved static protection strap. If one is not available, touch one hand to the chassis before 

contacting any other part of the charger. 

 

9. MOUNTING PROCEDURES 

 

 
 
 
 
 
 

The charger mounts to a wall or other vertical support. The mounting surface must safely support the charger’s 
weight, which is 25 pounds (11.3 kg), and also the weight of the fixed wiring. 

Mounting on a concrete surface: 

All mounting hardware is provided by the installer. 

Use optional ¾ inch thick, 18 in. x 24 in. sheet of marine plywood (not provided) to provide a suitable 
mounting surface for the charger. 

Drill four holes to secure the plywood to the wall using a minimum of four ¼ in. drive pin type expansion 
anchors to secure the plywood to the wall. Secure the plywood to the wall. 

Drill four holes using the mounting diagram on pg. 4 for ¼ in. (or M6) draw nut type expansion anchors 
through the plywood into the cement wall. 

Insert the four draw nut type expansion anchors through the plywood into the cement wall. 

Mount charger to draw nut type expansion anchors with nuts and flat washers. 

WARNING: 
THIS CHARGER IS INTENDED FOR COMMERCIAL AND INDUSTRIAL 
USE. ONLY TRAINED PERSONNEL WHO ARE QUALIFIED TO 
PERFORM ELECTRICAL INSTALLATIONS SHOULD INSTALL OR 
SERVICE THIS UNIT. 

WARNING: 
NEVER CHARGE STORAGE BATTERIES AT TEMPERATURES ABOVE 
OR BELOW THE LIMITS SPECIFIED BY THE BATTERY 
MANUFACTURER. NEVER ATTEMPT TO CHARGE A FROZEN BATTERY. 

7. MOUNTING LOCATION 

Содержание EnerGenius NRG22-10

Страница 1: ...y Charger SENS Part Number Document Revision DCN Number Date 101295 L 105749 July 28 2009 Installation or service questions Call SENS at 1 800 742 2326 303 678 7500 between 8 a m and 5 p m Mountain Ti...

Страница 2: ...gs on these products and on the engine A Someone should be within range of your voice or close enough to come to your aid when you work near a storage battery B Have plenty of fresh water and soap nea...

Страница 3: ...ber Breakout NRG 22 10 Model Output Output Input Voltage Alarm System Agency Category Voltage Current Frequency Code 12 12 volts 10 10 Amps H 120 208 240V C 5 Alarms L UL S Standard 24 24 volts 50 60...

Страница 4: ...WITH LOCAL ELECTRICAL CODES AND OTHER APPLICABLE INSTALLATION CODES B INSTALLATION MUST BE MADE ACCORDING TO THE INSTALLATION INSTRUCTIONS AND ALL APPLICABLE SAFETY REGULATIONS WARNING ONLY TRAINED A...

Страница 5: ...ected for service remove the output wiring in the reverse of the order given above D Be sure battery terminals are clean and properly tightened Be careful to keep corrosion from coming in contact with...

Страница 6: ...or battery owner s manual and make sure that the 12V 24V select jumper is set to the correct voltage 2 CHARGER LOCATION Do not set a battery or any other object on top of the charger This will obstru...

Страница 7: ...erconnects The above lengths are for operation at 25C For high temperature installations 40C reduce lengths by 10 In the case of high resistance in the cables to the battery the charger may cycle betw...

Страница 8: ...rger by the chassis only Remove the cover only when access is essential for installation and service and replace it promptly when finished B If possible wear an approved static protection strap If one...

Страница 9: ...nch pounds 10 WIRING A All wiring must comply with applicable codes and local ordinances See Section 5 for recommended gauges B The charger contains a DC output fuse for internal fault protection but...

Страница 10: ...KDOWN FIGURE 2A FIGURE 2B E Connect the AC line and neutral conductors at TB1 If there is an identified grounded circuit con ductor neutral attach it to the terminal marked N TB1 will accept 14 6 AWG...

Страница 11: ...K with no AC input TB5 6 FAIL Defaults to Fail with no AC input TB5 9 FAIL Defaults to OK with no AC input TB5 12 FAIL Defaults to OK with no battery TB5 15 FAIL Defaults to fail with no battery RELAY...

Страница 12: ...e 230V position for nominal mains voltages between 208V and 240V B Set the battery range jumper JP1A according to nominal battery voltage Use the 12V position for 12V batteries Use the 24V position fo...

Страница 13: ...SERVICE CONSULT THE BATTERY MANUFACTURER TO DETERMINE IF AND HOW THEY CAN BE SAFELY RESTORED TO SERVICE WARNING NEVER LEAVE A JUMPER IN THE JUMP POSITION DURING NORMAL OPERATION THIS DISABLES THE BATT...

Страница 14: ...onnect AC power then correct the jumper setting or battery voltage before proceeding E After a short delay typically 10 seconds or less the charger will produce output F If the meter display jumper is...

Страница 15: ...a ture increases The output voltage is clamped at 0 and 40 Degrees C to protect against extremely high or low output voltage See chart below Fault Tolerant The charger is protected from the following...

Страница 16: ...short circuit is removed In addition to detecting low battery voltage and short circuits the battery charger also monitors the peak voltage at its DC output terminals and will enter lockout if the DC...

Страница 17: ...On if Temperature Com pensation Working Off if Temperature Compen sation Option not used Confirm if temperature compensation is in tended to be used Only one sensor Local or re mote should be connect...

Страница 18: ...anch circuit breaker and any other disconnect devices 2 The meter display should light immediately after power on The green AC ON LED should be lighted If a temperature sensor is present either intern...

Отзывы: