background image

SENS EnerGenius Technical Manual  

14 

Service hotline: 1.800.742.2326 
                           1.303.678.7500  

See OPERATOR INSTRUCTION section for LED indicator definitions: 

A. Verify the status LEDs: 

AC FAIL

 should be 

ON

. If not, the DC output may be open or reversed, or the battery may be 

extremely discharged. 

BATT FAULT

 should be 

OFF

. If it lights, check for reversed polarity of the DC wiring. 

The 

DC LOW

 (Low Battery) LED may be either on or off, depending on the battery’s state of charge. 

All other LEDs and the meter display should be off. 

If the

 DC HIGH

 LED is on, check battery voltage jumper setting. 

B. Apply AC power by closing the branch circuit breaker and any other disconnect devices. 

C. The meter display should light immediately after power on. The green  

 

AC/ ON

 LED should be lighted. If a temperature sensor is present, either internal or remote, the green  

     

T-COMP

 (Temperature Compensation) LED should be lighted. 

D. If the 

BATT FAULT

 LED lights when AC is applied, this indicates that the battery voltage does not agree 

with the 

Range

 jumper setting. The charger is interlocked, and will not operate in this condition. 

Disconnect AC power, then correct the jumper setting or battery voltage before proceeding. 

E. After a short delay (typically 10 seconds or less), the charger will produce output.  

F. If the meter display jumper is selected to read Amps or automatic Volts/Amps: 

Current should be close to 10A if the battery requires recharging. If automatic boost is enabled, the 

BOOST MODE

 LED may light, in which case the battery will be charged until it reaches 106% of the 

float voltage. If boost is disabled, the green  

FLOAT MODE

 LED should be on and the battery will 

charge until it reaches the float voltage setting. 

Output current will be low if the battery is fully charged, possibly too low to read on the meter. This is 
normal, provided the correct charging voltage is present. The green  

FLOAT MODE

 LED should light 

when output current is below approximately 9 A (5A for single alarm). 

12. CHECK OUT 

* Active only on five alarm models - see page 3 for model number breakdown 

*Red for low battery voltage 

Red for low or missing AC input 

Green for normal voltage (float charge) 

Yellow for boost voltage (fast charge) 

Red for open, wrong voltage, or reversed battery 

Green for normal AC input 

*Red for excessive battery voltage 

Red for internal charger failure 

DC Volt/Amp Meter Display 

Green for temperature-corrected charger voltage 

Содержание EnerGenius NRG22-10

Страница 1: ...y Charger SENS Part Number Document Revision DCN Number Date 101295 L 105749 July 28 2009 Installation or service questions Call SENS at 1 800 742 2326 303 678 7500 between 8 a m and 5 p m Mountain Ti...

Страница 2: ...gs on these products and on the engine A Someone should be within range of your voice or close enough to come to your aid when you work near a storage battery B Have plenty of fresh water and soap nea...

Страница 3: ...ber Breakout NRG 22 10 Model Output Output Input Voltage Alarm System Agency Category Voltage Current Frequency Code 12 12 volts 10 10 Amps H 120 208 240V C 5 Alarms L UL S Standard 24 24 volts 50 60...

Страница 4: ...WITH LOCAL ELECTRICAL CODES AND OTHER APPLICABLE INSTALLATION CODES B INSTALLATION MUST BE MADE ACCORDING TO THE INSTALLATION INSTRUCTIONS AND ALL APPLICABLE SAFETY REGULATIONS WARNING ONLY TRAINED A...

Страница 5: ...ected for service remove the output wiring in the reverse of the order given above D Be sure battery terminals are clean and properly tightened Be careful to keep corrosion from coming in contact with...

Страница 6: ...or battery owner s manual and make sure that the 12V 24V select jumper is set to the correct voltage 2 CHARGER LOCATION Do not set a battery or any other object on top of the charger This will obstru...

Страница 7: ...erconnects The above lengths are for operation at 25C For high temperature installations 40C reduce lengths by 10 In the case of high resistance in the cables to the battery the charger may cycle betw...

Страница 8: ...rger by the chassis only Remove the cover only when access is essential for installation and service and replace it promptly when finished B If possible wear an approved static protection strap If one...

Страница 9: ...nch pounds 10 WIRING A All wiring must comply with applicable codes and local ordinances See Section 5 for recommended gauges B The charger contains a DC output fuse for internal fault protection but...

Страница 10: ...KDOWN FIGURE 2A FIGURE 2B E Connect the AC line and neutral conductors at TB1 If there is an identified grounded circuit con ductor neutral attach it to the terminal marked N TB1 will accept 14 6 AWG...

Страница 11: ...K with no AC input TB5 6 FAIL Defaults to Fail with no AC input TB5 9 FAIL Defaults to OK with no AC input TB5 12 FAIL Defaults to OK with no battery TB5 15 FAIL Defaults to fail with no battery RELAY...

Страница 12: ...e 230V position for nominal mains voltages between 208V and 240V B Set the battery range jumper JP1A according to nominal battery voltage Use the 12V position for 12V batteries Use the 24V position fo...

Страница 13: ...SERVICE CONSULT THE BATTERY MANUFACTURER TO DETERMINE IF AND HOW THEY CAN BE SAFELY RESTORED TO SERVICE WARNING NEVER LEAVE A JUMPER IN THE JUMP POSITION DURING NORMAL OPERATION THIS DISABLES THE BATT...

Страница 14: ...onnect AC power then correct the jumper setting or battery voltage before proceeding E After a short delay typically 10 seconds or less the charger will produce output F If the meter display jumper is...

Страница 15: ...a ture increases The output voltage is clamped at 0 and 40 Degrees C to protect against extremely high or low output voltage See chart below Fault Tolerant The charger is protected from the following...

Страница 16: ...short circuit is removed In addition to detecting low battery voltage and short circuits the battery charger also monitors the peak voltage at its DC output terminals and will enter lockout if the DC...

Страница 17: ...On if Temperature Com pensation Working Off if Temperature Compen sation Option not used Confirm if temperature compensation is in tended to be used Only one sensor Local or re mote should be connect...

Страница 18: ...anch circuit breaker and any other disconnect devices 2 The meter display should light immediately after power on The green AC ON LED should be lighted If a temperature sensor is present either intern...

Отзывы: