SENS EnerGenius Technical Manual
6
Service hotline: 1.800.742.2326
1.303.678.7500
-Battery
+Battery
Temperature Sensor
Alarm Contacts
Neutral
115/230VAC
Grounding
Conductor
Use wire routing devices to hold alarm and
temperature sensor conductors at least
1/4” (6.3 mm) away from power conductors.
ONE ALARM
MODEL
SHOWN- SEE PAGE 3
FOR MODEL NUM-
BER BREAKDOWN
G. Enable the automatic boost charge mode (equalizing charge) only if recommended by the battery manufacturer
H. Determine the voltage of the battery by referring to the engine or battery owner’s manual and make sure that
the 12V/24V select jumper is set to the correct voltage.
2. CHARGER LOCATION
Do not set a battery or any other object on top of the charger. This will obstruct the ventilation openings and
cause excessive heating. Ensure the charger is protected from blowing or dripping water.
3. GROUNDING INSTRUCTIONS
This battery charger should be connected to a grounded, metal, permanent wiring system; or an equipment
grounding conductor (earthing conductor) should be run with the circuit conductors and connected to the
equipment grounding terminal in the charger. This terminal is marked with the ground symbol. Connections to
the battery charger should comply with all local codes and ordinances.