DC
PV special
5K/6K/8K/10K 2.5~4
4
4~5
terminal
multi-core
12K/15K
outdoor
cable
(PV1-F)
Connecting
multi-core
5K/6K/8K/10K
NA
External
outdoor
12K/15K
Protection
cable
4~6
6
Ground
Cables
Table 5.2 Cable Max length at AC terminal
Model
5k/6k
8k
10k
12k
15k
Cross-sectional
Area
4mm
2
53m
40m
30m
25m
20m
6mm
2
80m
58m
47m
39m
30m
b. AC wiring terminals:
Leak-protective switch is not recommended in this system; if there is a must, please
install a model B switch with no less than 300mA current leakage. Neutral wire
sharing is forbidden for multi leak-protective switches in system, or tripping operation
will be resulted.
An independent three-phase circuit breaker must be installed on the AC side
of each inverter to ensure that the inverter can be safely disconnected from
WARNING
the power grid.
Do not connect loads between the AC output terminals of the inverter and
circuit breaker.
WARNING
30