USER MANUAL – Z-DAQ-PID
22
Lim Inf MSW
FP-32bit_MSW
R/W*
40018
Lim Inf LSW
FP-32bit_LSW
R/W*
40019
Output limiter lower limit (measure unit is the same of
output)
0
(=0 [mA])
Lim Sup MSW
FP-32bit_MSW
R/W*
40016
Lim Sup LSW
FP-32bit_LSW
R/W*
40017
Limit superior of the output limiter (measure unit is the same
of output)
1
(=20[mA])
PID-sign
Bit
R/W*
40007
PID regulation sign: 1=direct-type (cooling); 0=reverse-type
(heating)
0
Bit [7:0]
Proportional
Band
Word
R/W*
40025
PID regulation proportional band [%], with reference to the
Input Scale range (if operating modality=conversion with
PID)
100%
Integral time
Word
R/W*
40026
PID regulation integral time [sec/10]. 0=there is no integral
action (if operating modality=conversion with PID)
2400
[sec/10]
(=240sec)
Derivative time
Word
R/W*
40027
PID regulation derivative time [sec/10]. 0=there is no
derivative action (if operating modality=conversion with
PID)
0 [sec/10]
Set point MSW
FP-32bit_MSW
R/W*
40022
Set point LSW
FP-32bit_LSW
R/W*
40023
Input set point for the PID regulation [%] with reference to
the Input Scale range (if it is equal to 0, it corresponds to
the 0% of the Input Scale range; if it is equal to 1, it
corresponds to the 100% of the Input Scale range) (if
operating modality=conversion with PID)
50%
Process Value
MSW
FP-32bit_MSW
R
40103