USER MANUAL – Z-DAQ-PID
21
Output current type: 0=active current (the module supplies
the loop); 1=passive current (the sensor supplies the loop)
0
Bit 12
These bits aren’t used
/
Bit [11:9]
Output type: 0=current; 1=voltage
0
Bit 8
These bits aren’t used
/
Bit [7:1]
Output limiter: 0=deactivated; 1=activated
0
Bit 0
OUT-SS MSW
See “Output”
FP-32bit_MSW
R/W*
40012
OUT-SS LSW
FP-32bit_LSW
R/W*
40013
Output Start Scale: [mA] (if current-type output); [V] (if
voltage-type output)
0 [mA]
OUT-ES MSW
See “Output”
FP-32bit_MSW
R/W*
40014
OUT-ES LSW
FP-32bit_LSW
R/W*
40015
Output End Scale: [mA] (if current-type output); [V] (if
voltage-type output)
20 [mA]
OUT MSW
FP-32bit_MSW
R
40105
OUT LSW
FP-32bit_LSW
R
40106
Output value: [mA] (if current-type output); [V] (if voltage-
type output)
/
OUT
Word
R
40109
Output value: [µA] (if current-type output); [mV] (if voltage-
type output)
/
OUT-Fault
MSW
FP-32bit_MSW
R/W*
40020
OUT-Fault
LSW
FP-32bit_LSW
R/W*
40021
Fault output value (measure unit is the same of output)
Reg.40105,40106 are equal to reg.40020,40021 if
40069.2=1 (there is input burn-out error) (if out type =
analog)
0 [%]
OUT-Manual
Between: 0; 10000
Word
R/W*
40107
Output manual value [%
∙
100] (if it is equal to 0, it
corresponds to the 0% of the Output Scale range; if it is
equal to 10000, it corresponds to the 100% of the Output
Scale range); for selected output-type, see reg.40004 (if
operating modality=manual, constant output)
0 [%]