OUTPUT
Number
1
Resolution
14 bit
Signal-amplitude
limiting
The output signal can be amplitude-
limited by an “output limiter”
Voltage-type OUT
Configurable between: 0-5 V, 0-10 V (with minimum load resistance:
1 k
). Saturation value: 10.5 V
Current-type
OUT
(active or passive)
Configurable between: 0-20 mA, 4-20 mA (with maximum load
resistance: 600
). Saturation value: 21 mA. “Active current” =the
output: already powered on, needs to be connected to the passive
module; “passive current” =the output: powered off, needs to be
connected to the active module
Errors related to max
measuring range
Errors related
to max
measuring
range
Accuracy
Thermal
stability
Linearity
error
Voltage-type OUT
0.1%
0.01%/°K
0.01%
<1%
Voltage-type
OUT
(active or passive)
0.1%
0.01%/°K
0.01%
<1%
CONNECTIONS
RS485 interface
IDC10 connector
RS232 interface
Jack stereo 3.5 mm connector: plugs into COM port
1500 Vac ISOLATIONS
Between: power supply, ModBUS RS485, analog input,
analog output