USER MANUAL – Z-DAQ-PID
12
Filter applied to input
signal
0=deactivated
1-19=filtering values
40005.[7:0]
Rejection
0b00=50Hz rejection
0b01=60Hz rejection
0b10=Fast (no rejection)
40006.[9:8]
Operating mode setting
To set Z-DAQ-PID functioning modality characteristics, configure the following registers:
Description of register
Option/Meaning
Address
Functioning modality
0=Conversion with PID, analog output
1=Conversion without PID, analog output
2=Conversion with PID, ON/OFF output
3=Conversion without PID, ON/OFF
output
4=Manual, analog output
5=Manual, ON/OFF output
40007.[15:8]
Cycle time
Time in [sec/10]
(if output modality=ON/OFF)
40028
Minimum time of high-
state ON/OFF output
Time in [sec/10]
(if output modality=ON/OFF)
40029
Minimum time of low-state
ON/OFF output
Time in [sec/10]
(if output modality=ON/OFF)
40030
SlewRate enabling
0=deactivated
1=activated
40031
SlewRate
Value in [%/sec]
40032
PID regulation sign
1=direct-type (example: cooling)
0=reverse-type (example: heating)
40007.[7:0]