Technical data | Inverter
64 | Doc. No. 982056, Version 01, SelectSun 40K
Self consumption night (W)
< 0.5
AC terminal
Phoenix Contact T-LOX
knee lever connection TW50
AC cables
10 - 50 mm² (Aluminum / Copper)
AMBIENT CONDITIONS
Cooling
natural convection
Ambient Temperature at nominal power (°C)
-25 – +45 °C
Ambient Temperature (°C)
-25 – +60 °C
Storage Temperature (°C)
-25 – +60 °C
Transport Temperature (°C)
-25 – +60 °C
Rel. Air humidity (%)
4 – 100% (non-condensing)
Elevation (m above sea level)
4,000
Noise (dBA)
< 45
Environment classification (IEC 60721-3-4)
4K4H
Pollution degree (IEC 62109-6-3)
3
Type of protection (IEC 60529)
IP65
SAFETY AND PROTECTION FUNCTIONS
DC circuit breaker
integrated
Isolation monitoring
yes
Overload behaviour
DC working point adjustment
String Fuses
external
Grid monitoring
Voltage, Frequency, Anti Islanding, DC injection
Residual Current Monitoring (RCD)
yes
Internal Overvoltage Protection (EN 61643-11)
Type 3, integrated
Protection Class (IEC 62103)
I
Overvoltage Category (EN 60664-1)
DC: II, AC: III
GENERAL DATA
Interfaces
Ethernet, RS485, Sensor (Irradiation and
Temperature Sensor / external stop signal)
Dimensions W x H x D (mm)
755 x 820 x 300
Packaging dimensions W x H x D (mm)
795 x 950 x 510
Weight (kg)
75.6