Options | Irradiation and Temperature Sensor
56 | Doc. No. 982056, Version 01, SelectSun 40K
Fig. 23: Connection to two inverters (for AFCI variant)
In the AFCI variant, the irradiation and temperature sensor is connected individually to one inverter.
8.1.5
Configuration
The actual values of the sensor are shown on the display of the inverter at
Actual values > Sensor
.
The assignment of the sensor signals can be configures with PC configuration tool.
The data are recorded by the datalogger and are visible within the monitoring portal.
The actual values of the sensor can be viewed in
Actual values > Sensor
. The data continues to be
recorded with the data logger and can be viewed in the monitoring portal.
Note:
The shield of the sensor line (dotted line) must be applied to PIN 2 and PIN 5!
The outer diameter of the connecting cable can be max. 8 mm.
Note:
If you do not use the temperature input, wire a jumper across PIN 4 and
PIN 5. Alternatively, you can also wire the jumper to the intermediate terminal
point (cable extension).