XR30CX 

4/4 

15.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: XR30CX 

frontal 32x74 mm; depth 60mm; 

Mounting: XR30CX 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20; 

Frontal protection: XR30CX 

IP65 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply: 

according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%;  230Vac 

10%, 

50/60Hz, 110Vac 

10%, 50/60Hz

 

Power absorption: 

3VA max

 

Display

: 3 digits, red LED, 14,2 mm high; 

Inputs

: Up to 4 NTC or PTC probes.

 

Digital input: 

 free voltage contact 

Relay outputs: compressor 

SPST 8(3) A, 250Vac; or 20(8)A 250Vac

 

 

AUX: 

SPDT 8(3) A, 250Vac 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

2;

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0÷60 °C;

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F);  

PTC probe: 

-50÷150°C (-58÷302°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable);  

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit. 

16.

 

CONNECTIONS 

The X-REP

 

output

 

excludes

 the TTL output.. It’s present in the following codes:  

XR30CX- xx

2

xx, XR30CX –xx

3

xx; 

16.1

 

XR30CX – 8A COMPRESSOR 

N.C.

1 2 3 4 5

6

7

9 10 11 12

Comp

Light/

Alarm

R

oo

m

8

Hot Key/IV probe

TTL or X-REP output

8(3)A250V

8(3)A250V

Line

 

9-40Vdc supply

: connect to the terminals 7 and 8.

 

12Vac/dc supply

: connect to the terminals 7 and 8. 

24Vac/dc supply

: connect to the terminals 7 and 8. 

120Vac supply

: connect to the terminals 7 and 8. 

16.2

 

XR30CX – 20A COMPRESSOR 

 

N.C.

1 2 3 4 5

6

7

9 10 11 12

Comp

Light/

Alarm

R

oo

m

8

Hot Key/IV probe

TTL or X-REP output

8(3)A250V

20(8)A250V

Line

 

9-40Vdc supply

: connect to the terminals 7 and 8.

 

12Vac/dc supply

: connect to the terminals 7 and 8. 

24Vac/dc supply

: connect to the terminals 7 and 8. 

120Vac supply

: connect to the terminals 7 and 8. 

17.

 

DEFAULT SETTING VALUES  

Label 

Name 

Range 

°C/°F 

 

Set 

Set point 

LS÷US 

3.0 

- - - 

Hy 

Differential 

0,1

25.5°C/ 1

 255°F 

2.0 

Pr1 

LS 

Minimum set point 

-50°C

SET/-58°F

SET 

-50.0 

Pr2 

US 

Maximum set point 

SET

110°C/ SET 

 230°F 

110 

Pr2 

Ot 

Thermostat probe calibration 

-12

12°C /-120

120°F 

0.0 

Pr1 

P3P

 

Third probe presence 

n=not present; Y=pres. 

Pr2 

O3 

Third probe calibration 

-12

12°C /-120

120°F 

Pr2 

P4P 

Fourth probe presence 

n=not present; Y=pres. 

Pr2 

O4 

Fourth probe calibration 

-12

12°C /-120

120°F 

Pr2 

OdS 

Outputs delay at start up 

0÷255 min 

Pr2 

AC 

Anti-short cycle delay 

 50 min 

Pr1 

CCt 

Continuos cycle duration 

0.0÷24.0h 

0.0 

Pr2 

CCS 

Set point for continuous cycle 

 (-55.0÷150,0°C) (-67÷302°F) 

Pr2 

COn 

Compressor  ON  time  with  faulty 
probe 

 255 min 

15 

Pr2 

COF 

Compressor  OFF  time  with  faulty 
probe 

 255 min 

30 

Pr2 

CH 

Kind of action 

CL=cooling; Ht= heating 

cL 

Pr1 

CF 

Temperature measurement unit 

°C 

 °F 

°C  

Pr2 

rES 

Resolution 

in=integer; dE= dec.point

 

dE  

Pr1 

dLy 

Display temperature delay   

0 ÷ 20.0 min  (10 sec.)  

Pr2 

IdF 

Interval between defrost cycles 

 120 ore 

Pr1 

MdF 

(Maximum) length for defrost 

 255 min 

20 

Pr1 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it 

Pr2 

dAd 

MAX display delay after defrost 

0 ÷ 255 min 

30 

Pr2 

ALc 

Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab 

Pr2 

ALU 

MAXIMUM temperature alarm 

Set

110.0°C; Set÷230°F 

110 

Pr1 

ALL 

Minimum temperature alarm 

-50.0°C

Set/ -58°F

Set 

-50.0 

Pr1 

AFH 

Differential for temperat. alarm 
recovery 

(0,1°C÷25,5°C) (1°F÷45°F) 

Pr2 

ALd 

Temperature alarm delay 

 255 min 

15 

Pr2 

dAo 

Delay of temperature alarm at start 
up 

 23h e 50’ 

1.3 

Pr2 

AP2 

Probe for temperat. alarm of 
condenser 

nP; P1; P2; P3; P4 

P4 

Pr2 

AL2 

Condenser for low temperat. alarm  (-55 ÷ 150°C) (-67÷ 302°F) 

-40 

Pr2 

AU2 

Condenser for high temperat. alarm  (-55 ÷ 150°C) (-67÷ 302°F) 

110 

Pr2 

AH2 

Differ.  for  condenser  temp.  alar. 
recovery 

[0,1°C ÷ 25,5°C]  [1°F ÷ 

45°F] 

Pr2 

Ad2 

Condenser  temperature  alarm 
delay  

 0 ÷ 254 (min.) , 255=nU 

15 

Pr2 

dA2 

Delay  of  cond.  temper.  alarm  at 
start up 

0.0 ÷ 23h  50’ 

1,3 

Pr2 

bLL 

Compr.  off  for  condenser  low 
temperature alarm 

n(0) - Y(1) 

Pr2 

AC2 

Compr.  off  for  condenser  high 
temperature alarm 

n(0) - Y(1) 

Pr2 

tbA 

Alarm relay disabling 

n=no; y=yes 

Pr2 

oA1 

2

nd

 relay configuration 

ALr = alarm; dEF = do not 

select it; Lig =Light; AUS 

=AUX; onF=always on; Fan= 

do not select it; db = do not 

select it; dF2 = do not select it 

Lig  

Pr2 

AoP 

Alarm relay  polarity  (oA1=ALr) 

oP; cL 

cL 

Pr2 

i1P 

Digital input polarity 

oP=opening;CL=closing 

cL 

Pr1 

i1F 

Digital input configuration 

EAL, bAL, PAL, dor; dEF; Htr, 
AUS 

dor 

Pr1 

did 

Digital input alarm delay 

0÷255min 

15 

Pr1 

nPS 

Number  of  activation  of  pressure 
switch 

0 ÷15  

15 

Pr2 

odc 

Compress status when open door 

no; Fan; CPr; F_C  

no 

Pr2 

rrd 

Regulation restart with door open 
alarm 

n – Y 

Pr2 

HES 

Differential for Energy Saving 

 (-30°C÷30°C) (-54°F÷54°F) 

Pr2 

Adr 

Serial address 

0÷247 

Pr2 

PbC 

Kind of probe 

Ptc; ntc 

ntc 

Pr1 

onF 

on/off key enabling 

nu, oFF; ES 

nu 

Pr2 

dP1 

Room probe display 

-- 

 -- 

Pr2 

dP3 

Third probe display 

-- 

 -- 

Pr1 

dP4 

Fourth probe display 

-- 

 -- 

Pr1 

rSE 

Real set point value 

actual set 

 -- 

Pr2 

rEL 

Software release 

-- 

 -- 

Pr2 

Ptb 

Map code 

-- 

 -- 

Pr2 

 

 
 

Содержание 2000150

Страница 1: ...98 REV 0 07 2020 J P SELECTA s a u Autov a A 2 Km 585 1 Abrera 08630 Barcelona Espa a Tel 34 937 700 877 Fax 34 937 702 362 e mail selecta jpselecta es website http www jpselecta es C MARA REFRIGERADO...

Страница 2: ...Dixell controller 4 14 Functions 4 15 Setting the controllers offset value 4 16 Trouble shooting 5 INDEX SAFETY INFORMATIONS 6 USER INSTRUCTIONS 7 1 Environmental protection and disposal 7 2 Safety i...

Страница 3: ...y o explosivos no deben almacenarse en el congelador Todas las unidades deben recibir instrucciones de instalaci n y de funcionamiento Adem s de la instalaci n con los espacios libres las instruccione...

Страница 4: ...to 2 Instrucciones de seguridad Para evitar lesiones y da os al equipo deben desembalarlo y configurarlo m nimo dos personas Si al desembalarlo observa que el equipo est deteriorado no lo conecte a la...

Страница 5: ...iento del congelador El congelador vac o debe estar encendido durante al menos 24 horas antes de cargarlo El congelador no debe cargarse por encima de las paredes interiores que indica el l mite de la...

Страница 6: ...y suelte inmediatamente la tecla SET o espere 5 segundos para mostrar nuevamente el valor de la sonda C mo bloquear y desbloquear el teclado 1 Pulse las teclas Arriba y Abajo simult neamente durante...

Страница 7: ...mbiente es demasiado alta Se ha cargado recientemente el aparato con una gran cantidad de productos calientes La temperatura dentro del equipo es demasiado alta Por favor compruebe si El controlador D...

Страница 8: ...ble gasses and explosives must not be stored in the freezer All units should be provided with installation and operating instructions In addition to the Clearances Installation the instructions should...

Страница 9: ...Fig 1 2 Safety instructions In order to prevent injuries and or damage to the appliance it should be unpacked and set up by min two people If upon unpacking the appliance is found damaged do not conn...

Страница 10: ...eezer The empty freezer should be switched on for at least 24 hours prior to loading of the freezer The freezer should not be loaded above the inside walls which is also the load line limit Please not...

Страница 11: ...than 3 seconds How to change the set point 1 Press the SET key for more than 3 seconds to change the set point value 2 The set point value will be displayed and the LED starts flashing 3 To change the...

Страница 12: ...Dixell controller set to the correct temperature Has an excess amount of ice formed inside the appliance If you have checked the above points and the appliance is still not working as expected please...

Страница 13: ...de una temperatura Opcionalmente la entrada digital puede convertirse en una tercera entrada de sonda La salida HOT KEY permite conectar la unidad por medio del m dulo externo XJ485 CX a una red compa...

Страница 14: ...urante el ciclo continuo se utiliza este set point COn Tiempo compresor ON con fallo de sonda 0 255 min tiempo durante el cual el compresor est operando en caso de fallo de sonda Con COn 0 el compreso...

Страница 15: ...r Realiza un deshielo si las condiciones son adecuadas Despu s del deshielo haya terminado la regulaci n normal se restablecer solo si la entrada digital se deshabilita de otro modo el instrumento deb...

Страница 16: ...inales 7 y 8 120Vac conectar l alimentaci n a los terminales 7 y 8 16 2 XR30C COMPRESOR 20A N C 1 2 3 4 5 6 7 9 10 11 12 Comp Light Alarm Room 8 Hot Key IV probe TTL or X REP output 8 3 A250V 20 8 A25...

Страница 17: ...0 255 min 15 Pr1 nPS N mero activaci nes para la funci n pres stato 0 15 15 Pr2 OdC Control de puerta abierta no FAn CP F C no Pr2 rrd Regulaci n despu s alarma de puerta abierta n Y y Pr2 HES Difere...

Страница 18: ...to display a temperature The digital input can operate as third temperature probe The HOT KEY output allows to connect the unit by means of the external module XJ485 CX to a network line ModBUS RTU co...

Страница 19: ...OFF in case of faulty thermostat probe With COF 0 compressor is always active CH Type of action CL cooling Ht heating DISPLAY CF Temperature measurement unit C Celsius F Fahrenheit WARNING When the me...

Страница 20: ...P can be connected to the instrument trough the HOY KEY connector The X REP output EXCLUDES the serial connection To connect the X REP to the instrument the following connectors must be used CAB 51F 1...

Страница 21: ...delay at start up 0 255 min 0 Pr2 AC Anti short cycle delay 0 50 min 1 Pr1 CCt Continuos cycle duration 0 0 24 0h 0 0 Pr2 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 3 Pr2 COn Compressor...