1592020030 XR30CX GB m&M r1.1 27.03.2015 

XR30CX 

3/4 

If the nPS activation in the did time is reached, switch off and on the instrument to 
restart normal regulation. 

odc  Compressor status with door open:

  

no,

 

Fan

 = normal; 

CPr

F_C

 = Compressor OFF.  

rrd  Outputs restart after doA alarm: no = 

outputs not affected by the doA alarm;  

yES = 

outputs restart with the doA alarm;  

HES Temperature increase during the Energy Saving cycle :

 (-30,0°C

30,0°C/-22÷86°F) 

it sets the increasing value of the set point during the Energy Saving cycle.  

OTHER 
Adr  Serial  address

  (1÷244):  Identifies  the  instrument  address  when  connected  to  a 

ModBUS compatible monitoring system. 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC 

probe, 

ntc = 

NTC probe. 

onF  on/off key enabling: nu = 

disabled; 

oFF = 

enabled; 

ES = not set it

dP1  Thermostat probe display 
dP3  Third probe display

optional

dP4  Fourth probe display

rSE  Real  set  point: 

(readable  only),  it  shows  the  set  point  used  during  the  energy  saving 

cycle or during the continuous cycle. 

rEL  Software release 

for internal use

Ptb  Parameter table code: 

readable only

8.

 

DIGITAL INPUT (ENABLED WITH P3P = N) 

The free voltage digital input is programmable in different configurations by the “

i1F

” 

parameter. 

8.1

 

DOOR SWITCH INPUT  (i1F = dor) 

It  signals  the  door  status  and  the  corresponding  relay  output  status  through  the  “

odc

” 

parameter: 

no,

 

Fan

 = normal (any change); 

CPr, 

  

F_C

 = Compressor OFF. 

Since the door is opened, after the delay time set through parameter “

did

”, the door alarm is 

enabled, the display shows the message “

dA

” and 

the regulation restarts is rtr = yES.

 The 

alarm stops as soon as the external digital input is disabled again. With the door open, the 
high and low temperature alarms are disabled. 

8.2

 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling 

the  “

EAL

”  alarm message.  The  outputs status don’t  change.  The  alarm stops  just  after the 

digital input is de-activated. 

8.3

 

SERIOUS ALARM MODE (i1F = bAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

CA

” 

alarm  message.  The  relay  outputs  are  switched  OFF.  The  alarm  will  stop  as  soon  as  the 
digital input is de-activated. 

8.4

 

PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number 

of activation of  the “

nPS

” parameter, the “

CA

” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is 
always OFF. 

If  the  nPS  activation  in  the  did  time  is  reached,  switch  off  and  on  the  instrument  to 
restart normal regulation. 

8.5

 

START DEFROST (i1F = dFr) 

It  starts  a  defrost  if  there  are  the  right  conditions.  After  the  defrost  is  finished,  the  normal 
regulation will restart only if the digital input is disabled otherwise the instrument will wait until 
the “MdF” safety time is expired. 

8.6

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F = Htr) 

This  function  allows  to  invert  the  regulation  of  the  controller:  from  cooling  to  heating  and 
viceversa. 

8.7

 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ 
HES (parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The  TTL  serial  line,  available  through  the  HOT  KEY  connector,  allows  by  means  of  the 
external TTL/RS485 converter, 

XJ485-CX

, to connect the instrument to a monitoring system 

ModBUS-RTU

 compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the HOY 
KEY connector. The X-REP output 

EXCLUDES 

 the serial connection.

 

 

To connect the X-REP to the 
instrument the following 
connectors must be used CAB-
51F(1m), CAB-52F(2m), CAB-
55F(5m), 

11.

 

INSTALLATION AND MOUNTING 

 

Instrument 

XR30CX

 shall be mounted on vertical panel, in a 

29x71 mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 0

60 

°C.  Avoid  places  subject  to  strong  vibrations,  corrosive 
gases,  excessive  dirt  or  humidity.  The  same 
recommendations  apply  to  probes.  Let  air  circulate  by  the 
cooling holes. 
 

12.

 

ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up 
to  2,5  mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the 

instrument’s requirements. Separate the probe cables from the power supply cables, from the 
outputs  and  the  power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each 
relay, in case of heavier loads use a suitable external relay. 

12.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 
infiltration. It is recommended to place the thermostat probe away from air streams to correctly 
measure  the  average  room  temperature.  Place  the  defrost  termination  probe  among  the 
evaporator fins in the coldest place, where most ice is formed, far from heaters or from the 
warmest place during defrost, to prevent premature defrost termination. 

13.

 

HOW TO USE THE HOT KEY  

13.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message 

appears followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 key 

if you want to restart the upload again or remove the “

Hot key

” to abort the operation. 

13.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert    a 

programmed  “Hot  Key”  into  the  5  PIN  receptacle 

and  then  turn  the 

Controller ON. 

3.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Controller 

memory, the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and 

then  on  if  you  want  to  restart  the  download  again  or  remove  the  “

Hot  key

”  to  abort  the 

operation. 

14.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and 
“COF” 

“P3” 

Third probe  failure 

Outputs unchanged 

“P4” 

Fourth probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the “Ac2” parameter 

"LA2" 

Condenser low temperature 

It depends on the “bLL” parameter 

“dA” 

Door open 

Compressor according to rrd 

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious 

external 

alarm 

(i1F=bAL) 

All outputs OFF. 

“CA” 

Pressure 

switch 

alarm 

(i1F=PAL) 

All outputs OFF 

14.1

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P3

” and “

P4

” start some seconds after the fault in the related probe; they 

automatically  stop  some  seconds  after  the  probe  restarts  normal  operation.  Check 
connections before replacing the probe. 
Temperature  alarms  “

HA

”,  “

LA

”  “

HA2

”  and  “

LA2

”  automatically  stop  as  soon  as  the 

temperature returns to normal values. 
Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is disabled. 

Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

14.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

noA 

None alarm is recorded.

 

Содержание 2000150

Страница 1: ...98 REV 0 07 2020 J P SELECTA s a u Autov a A 2 Km 585 1 Abrera 08630 Barcelona Espa a Tel 34 937 700 877 Fax 34 937 702 362 e mail selecta jpselecta es website http www jpselecta es C MARA REFRIGERADO...

Страница 2: ...Dixell controller 4 14 Functions 4 15 Setting the controllers offset value 4 16 Trouble shooting 5 INDEX SAFETY INFORMATIONS 6 USER INSTRUCTIONS 7 1 Environmental protection and disposal 7 2 Safety i...

Страница 3: ...y o explosivos no deben almacenarse en el congelador Todas las unidades deben recibir instrucciones de instalaci n y de funcionamiento Adem s de la instalaci n con los espacios libres las instruccione...

Страница 4: ...to 2 Instrucciones de seguridad Para evitar lesiones y da os al equipo deben desembalarlo y configurarlo m nimo dos personas Si al desembalarlo observa que el equipo est deteriorado no lo conecte a la...

Страница 5: ...iento del congelador El congelador vac o debe estar encendido durante al menos 24 horas antes de cargarlo El congelador no debe cargarse por encima de las paredes interiores que indica el l mite de la...

Страница 6: ...y suelte inmediatamente la tecla SET o espere 5 segundos para mostrar nuevamente el valor de la sonda C mo bloquear y desbloquear el teclado 1 Pulse las teclas Arriba y Abajo simult neamente durante...

Страница 7: ...mbiente es demasiado alta Se ha cargado recientemente el aparato con una gran cantidad de productos calientes La temperatura dentro del equipo es demasiado alta Por favor compruebe si El controlador D...

Страница 8: ...ble gasses and explosives must not be stored in the freezer All units should be provided with installation and operating instructions In addition to the Clearances Installation the instructions should...

Страница 9: ...Fig 1 2 Safety instructions In order to prevent injuries and or damage to the appliance it should be unpacked and set up by min two people If upon unpacking the appliance is found damaged do not conn...

Страница 10: ...eezer The empty freezer should be switched on for at least 24 hours prior to loading of the freezer The freezer should not be loaded above the inside walls which is also the load line limit Please not...

Страница 11: ...than 3 seconds How to change the set point 1 Press the SET key for more than 3 seconds to change the set point value 2 The set point value will be displayed and the LED starts flashing 3 To change the...

Страница 12: ...Dixell controller set to the correct temperature Has an excess amount of ice formed inside the appliance If you have checked the above points and the appliance is still not working as expected please...

Страница 13: ...de una temperatura Opcionalmente la entrada digital puede convertirse en una tercera entrada de sonda La salida HOT KEY permite conectar la unidad por medio del m dulo externo XJ485 CX a una red compa...

Страница 14: ...urante el ciclo continuo se utiliza este set point COn Tiempo compresor ON con fallo de sonda 0 255 min tiempo durante el cual el compresor est operando en caso de fallo de sonda Con COn 0 el compreso...

Страница 15: ...r Realiza un deshielo si las condiciones son adecuadas Despu s del deshielo haya terminado la regulaci n normal se restablecer solo si la entrada digital se deshabilita de otro modo el instrumento deb...

Страница 16: ...inales 7 y 8 120Vac conectar l alimentaci n a los terminales 7 y 8 16 2 XR30C COMPRESOR 20A N C 1 2 3 4 5 6 7 9 10 11 12 Comp Light Alarm Room 8 Hot Key IV probe TTL or X REP output 8 3 A250V 20 8 A25...

Страница 17: ...0 255 min 15 Pr1 nPS N mero activaci nes para la funci n pres stato 0 15 15 Pr2 OdC Control de puerta abierta no FAn CP F C no Pr2 rrd Regulaci n despu s alarma de puerta abierta n Y y Pr2 HES Difere...

Страница 18: ...to display a temperature The digital input can operate as third temperature probe The HOT KEY output allows to connect the unit by means of the external module XJ485 CX to a network line ModBUS RTU co...

Страница 19: ...OFF in case of faulty thermostat probe With COF 0 compressor is always active CH Type of action CL cooling Ht heating DISPLAY CF Temperature measurement unit C Celsius F Fahrenheit WARNING When the me...

Страница 20: ...P can be connected to the instrument trough the HOY KEY connector The X REP output EXCLUDES the serial connection To connect the X REP to the instrument the following connectors must be used CAB 51F 1...

Страница 21: ...delay at start up 0 255 min 0 Pr2 AC Anti short cycle delay 0 50 min 1 Pr1 CCt Continuos cycle duration 0 0 24 0h 0 0 Pr2 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 3 Pr2 COn Compressor...