38
TB XRN2 02.00 E
Setting list
XRN2
Project:
SEG job.-no.:
Function group: =
Location: +
Relay code: -
Relay functions:
Password:
Function
Unit
Default
settings
Actual
settings
∆
/Y
input transformer connection
Y
U<
pickup value for undervoltage element (low set)
V
90/210/360*
t
U
<
tripping delay for undervoltage element
s
0.04
U<<
pickup value for undervoltage element (high set)
V
80/190/320*
t
U
<<
tripping delay for undervoltage element
s
0.04
U>
pickup value for overvoltage element (low set)
V
110/250/440*
t
U
>
tripping delay for overvoltage element
s
0.04
U>>
pickup value for overvoltage element (high set)
V
120/270/480*
t
U
>>
tripping delay for overvoltage element
s
0.04
f
N
rated frequency
Hz
50
T
frequency measuring repetition in periods
cycles
4
f
1
pickup value for frequency element 1
Hz
4800
t
f1
tripping delay for frequency element 1
s
0.1
f
2
pickup value for frequency element 2
Hz
4900
t
f2
tripping delay for frequency element 2
s
0.1
f
3
pickup value for frequency element 3
Hz
5100
t
f3
tripping delay for frequency element 3
s
0.1
df
pickup value for rate of frequency (dt/dt) in
Hz/s
EXIT
dt
measuring repetition for df/dt
periods
2
1/3
vector surge tripping logic
1PH
∆Θ
pickup value for vector surge
°
2.0
U
B
<
voltage threshold value for frequency and vector
surge measuring (or df/dt)
V
10/23/40*
RS
Slave address of the serial interface
1
* thresholds dependent on rated voltage 100 V / 230 V / 400 V