background image

Troubleshooting

 

*

 

www.lutron.com

Load does 
not respond 
to Wireless 
Transmitter(s)

•  Ensure breaker to the PowPak

®

 Relay Module 

is on.

•  Ensure the load has been properly wired to the 

PowPak

®

 Relay Module.

•  Ensure Wireless Transmitter is properly 

associated to PowPak

®

 Relay Module.

•  Ensure Wireless Transmitter’s battery is installed 

correctly.

Wireless 
Transmitter(s) 
cannot be 
associated 
to PowPak

®

 

Relay Module

•  The maximum number of Wireless Transmitters 

have been associated to the PowPak

®

 Relay 

Module. To remove a previously set up Wireless 
Transmitter, tap the button used for association 
on the Wireless Transmitter three times, on the 
third tap hold for three seconds and then tap 
three more times.

Unaffected Mode

Unaffected Mode allows a system with an Occupancy Sensor 
associated to multiple Relay Modules to be set up such that only 
selected loads turn on automatically. Other loads will require a 
manual turn-on with a Pico

R

 Remote Control. All loads will turn off 

automatically when the room is vacated. 

On a Relay Module, press and hold both the Relay Toggle and 
Advanced Operations (“ADV”) buttons for 6 seconds until the 
LED begins flashing quickly.

On the associated Occupancy Sensor, press and hold the 
“Test” button* for 6 seconds until the lens flashes.

Unaffected mode will be exited automatically. This Relay 
Module will now be unaffected by occupancy commands. 
Repeat procedure for any additional devices.

 

* If no “Test” button, hold “Lights On” button.

        Note: 

The CCO cannot be made unaffected.

Reset Factory Defaults

 

 Note:

 In some instances it may be necessary to reset the 

PowPak

®

 Relay Module back to factory default settings. 

Triple-tap the “CNTRL” button on the Relay Module and hold 
until the LED begins to flash slowly.

Within 3 seconds of flashing, release and triple-tap the button 
again and the LED will flash rapidly indicating that the unit has 
been reset to factory defaults.

 Note: 

Any associations or programming previously set up with 

the unit will be lost and will need to be re-programmed.

Test

Link

Test

Link

Cal.

CCO Information

   Some PowPak

®

 Relay Modules include a dry contact closure 

output that provides occupancy status to 3rd-party equipment 
such as building management systems, HVAC, and VAV 
controllers. 

   CCO provides both normally open (NO) and normally closed (NC) 

maintained-type outputs.

   CCO rated to switch resistive loads at 

voltages up to 24 V only. To properly 
control inductive load types such as 
relays, solenoids, or motors, refer to 
Application Note #434.

Switching 
Voltage

0-24 V

-

0-24 V

~

Resistive 
Load

 

1.0 A
0.5 A

R

Test

Link

Cal.

Part of the Energi TriPak

®

 Family

PowPak

®

 | Installation

Relay Module

English

Lutron Electronics Co., Inc. | 7200 Suter Road 
Coopersburg, PA 18036-1299, U.S.A.

041504 
Rev. A 
09/2015

Need Help? www.lutron.com or call the Lutron Technical Support Center, at 1.800.523.9466

For each system ensure you have:

At least one PowPak

®

 Relay Module.

At least one Wireless Transmitter. 

Required Components

Start Here

Limited Warranty

(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For 
warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.

This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase. 
This warranty does not cover the cost of installtion, removal or reinstallation, or damage resulting from misuse, abuse, or damage from 
improper wiring or installation. This warranty does not cover incidental or consequential damages. 

LUTRON’S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE 
MANUFACTURE, SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER EXCEED THE PURCHASE 
PRICE OF THE UNIT.

This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow 
the exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above 
limitations may not apply to you. 

Lutron, Energi TriPak, Pico, PowPak and Softswitch are registered trademarks and Radio Powr Savr and Vive are trademarks of Lutron 
Electronics Co., Inc. ©2012-2015 Lutron Electronics Co., Inc.

1

When installing a PowPak

R

 Relay Module,  

use the supplied conduit nut and wire the module 
as shown.

Install PowPak

R

 Relay Module

Associate Wireless Transmitters to PowPak

R

 20 A Relay Module 

*

Hold the Relay Toggle  
button on the PowPak

®

  

Relay Module for 6 seconds  
to enter association mode.

Before beginning this step, make sure that there are no other PowPak

®

 modules being set up within the same building. It is possible that Wireless Transmitters 

from other systems can be incorrectly associated to this system.

2

3

Permanently Install  
Wireless Transmitters

Note:

 Please consult individual component 

installation guides for information.

RMJS-16R-DV-B | URMJS-16R-DVB 

With Softswitch

®

 

 

RMJS-16RCCO1DV-B | URMJS-16RCCO1DVB   

With Softswitch

® 

 and Occupancy-Status CCO

 

120 / 277  V

~

  50 / 60 Hz  16 A   

1/2 HP at 120 V

~  

1

1

2

 HP at 277 V

~

UL 2043 Plenum Rated

RMJS-5R-DV-B 

RMJS-5RCCO1-DV-B

   

With Occupancy-Status CCO

 

120 / 277  V

~

  50 / 60 Hz  5 A   

1/6 HP at 120 V

~  

1/3 HP at 277 V

~

UL 2043 Plenum Rated

Shock Hazard. May result in serious injury or death.  

Turn off power at circuit breaker before installing the unit.

WARNING

All Wireless Transmitters must be installed within  
30 ft (9 m) of the PowPak

®

 Relay Module.

 

Radio Powr Savr

TM  

Occupancy  

Sensor

30 ft (9 m) 

Maximum

40 ft (12 m)

30 ft (9 m)

PowPak

®

 

Relay Module

 

Install in center of room to  

maximize RF coverage.

Pico

®

  

Remote 
Control

FCC / IC  Information:

This device complies with part 15 of the FCC Rules and Industry Canada licence-exempt 
RSS standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and
(2)  this device must accept any interference, including interference that may cause undesired 

operation.

Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user’s 
authority to operate this equipment. 

NOTE: 

This equipment has been tested and found to comply with the limits for a Class 

B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide 
reasonable protection against harmful interference in a residential installation. This equipment 
generates, uses and can radiate radio frequency energy and, if not installed and used in 
accordance with the instructions, may cause harmful interference to radio communications. 
However, there is no guarantee that interference will not occur in a particular installation. If 
this equipment does cause harmful interference to radio or television reception, which can be 
determined by turning the equipment off and on, the user is encouraged to try to correct the 
interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
•  Connect the equipment into an outlet on a circuit different from that to which the receiver is 

connected.

Radio Powr Savr

TM

 Occupancy  

Sensor (10 maximum)

PowPak

®

 Relay Module

Load  
Status  
LED

Relay Toggle

Advanced 
Operations

Contact 
Closure 
Output 
(CCO)
(Class 2)

(Occupancy-Status CCO Option Shown)

Relay Module 
without 
occupancy-status 
CCO also 
available.

If installing unit inside a junction box please  
see Application Note #423.

For more information:

  

www.lutron.com/powpakrelay

120/277 V

50/60 Hz

Conduit Nut

White

  

(Neutral)

Black

  

(Line/Hot)

Red

  

(Switched  
Line/Hot)

Note:

 When wiring a CCO model

 

to 3rd-party  

systems, use 20 AWG to 16 AWG (0.5 mm

to 

1.5 mm

2

) solid or stranded wire.

To 3rd Party Equipment

To Load

NO

(Normally Open)

NC

(Normally Closed)

COM

(Common)

NC

(Normally Closed)

CCO operation affected only by  
associated occupancy or vacancy sensors.

Room Occupied:

 

NO = Close  NC = Open

Room Unoccupied:

  NO = Open  NC = Close

Suggested Installation Location:

Install in center of room.  

This ensures proper RF coverage of area.

Hold the indicated button on a Wireless Transmitter for  
6 seconds to associate the device.* 
Repeat for any additional Wireless Transmitters.

Hold the Relay Toggle button on the PowPak

®

  

Relay Module for 6 seconds to save association(s).

* If no 

g

 button, hold “Lights Off” button.

Note:

 The load will flash once after each 

step to confirm successful completion.

Test

Link

Daylight Sensor setup 

*

Calibration

Turn lights in room on using the Relay 
Toggle button on the PowPak

®

 Relay 

Module or an associated Pico

®

Press & hold “Cal.” on the associated 
Daylight Sensor for 6 seconds.

Exit room for 5 minutes to allow 
calibration to be completed.

           

Note:

 When calibration has completed, all 

lights will flash and the system will begin 
daylighting.

If it is desired to have multiple zones of  
lights turn on at different daylight levels  
(using multiple Relay Modules with one  
Daylight Sensor) follow the Tuning 
procedure described in the Daylight Sensor 
(LRF2-DCRB) installation instructions.  

 

Use the Relay Toggle button in place of the  
Dimmer/Switch tap button referenced in  
the document.

Tuning (Optional)

4

Radio Powr Savr

TM

 

Daylight Sensor
(1 maximum)

Pico

®

  

Remote Control  
(10 maximum)

Note for Replacement:

RMxS and URMxS - the "S" model can replace the non-"S" model

*

   For set-up, programming, and troubleshooting with a Vive

TM

 

system, please refer to the installation instructions included 
with the Vive

TM

 hub or at www.lutron.com

 

Important Notes:

 

Please read before installing.

• 

For installation by a qualified electrician in accordance with all local and  

 

national electrical codes. 

• 

Note:

 Use copper conductors only.

• 

Check to see that the device type and rating is suitable for the application.

• 

DO NOT

 install if product has any visible damage.

• 

 If moisture or condensation is evident, allow the product to dry completely

 before 

installation.

• 

Operate between 32 °F (0 °C) and 131 °F (55 °C).

• 

0% to 90% humidity, non-condensing.

• 