I2> . tChar
[Protection Para / I2>]
0.1
Only available if:
• I2> . Char = IEC NINV
•
• I2> . Char = IEC VINV
•
• I2> . Char = IEC EINV
•
• I2> . Char = IEC LINV
•
• I2> . Char = RINV
•
• I2> . Char = HV Fuse
•
• I2> . Char = FR Fuse
•
• I2> . Char = IEEE MINV
•
• I2> . Char = IEEE VINV
•
• I2> . Char = IEEE EINV
•
• I2> . Char = EF Curve
•
0.05 . . . 10.00
P.1
Time multiplier/tripping characteristic factor. The setting range depends on the selected tripping curve.
I2> . tMin
[Protection Para / I2>]
0.00s
Only available if:
• I2> . Char = IEC NINV
•
• I2> . Char = IEC VINV
•
• I2> . Char = IEC EINV
•
• I2> . Char = IEC LINV
•
• I2> . Char = RINV
•
• I2> . Char = HV Fuse
•
• I2> . Char = FR Fuse
•
• I2> . Char = IEEE MINV
•
• I2> . Char = IEEE VINV
•
• I2> . Char = IEEE EINV
•
• I2> . Char = EF Curve
•
0.00s . . . 20.00s
P.1
Minimum trip delay time. Independent of the measured current values, the trip delay time does never fall below the
minimum that is set here.
56
WIC1
WIC1-1.0-EN-REF
7 Protection Parameter
7.13.2 I2>: Settings