Alarm
The function operates as a supervision function, i.e. a fault generates neither alarm nor
trip, but an »Alarm« signal gets issued instead.
Out. Mode
Select whether the output shall operate as an impulse output (for connecting a flag indicator
with full compatibility to the 1st generation WIC1), or as a relay output (with a fixed,
pre-defined usage as a self-supervision contact). \n(The usage as a self-supervision contact
is only possible with an externally supplied WIC1-4, and connecting a flag indicator is not
permissible with this setting.)
Selection list referenced by the following parameters:
•
•
Out. Mode
Description
Impulse Output
The output shall operate as an impulse output (for connecting a flag indicator with full
compatibility to the 1st generation WIC1).
Syst. O.K. & Ext.Suppl.
The output shall operate as as a self-supervision output, together with an external
output relay. (See the User Manual chapter “Technical Data” for the specification of a
compatible output relay).
The signal at this output indicates that the WIC1 is running and is supplied by external
auxiliary power and has loaded sufficient electrical energy for triggering the trip impulse
output.
Relay Output
The output shall operate as as a relay output (for connecting an output relay).
Selection list referenced by the following parameters:
•
╚═▷ DiggiMEC . FI / BO 1 assign.
•
•
╚═▷ DiggiMEC . FI / BO 2 assign.
•
•
╚═▷ DiggiMEC . FI / BO 3 assign.
•
•
•
•
•
•
•
• [ . . . ]
•
Description
“-”
IH2 . Block. L1
Signal: Inrush blocking of phase L1 of the phase overcurrent protection
IH2 . Block. L2
Signal: Inrush blocking of phase L2 of the phase overcurrent protection