CT . CT Shift by 0°/180°
[Field Para / CT]
0°
0°, 180°
P.1
If this is set to 180° the phase current vectors are shifted by 180 degrees (change of sign), by device-internal
calculation, i.e. without modification of the wiring.
CT . ECT Shift by 0°/180°
[Field Para / CT]
0°
Avail. depends on device type.
0°, 180°
P.1
If this is set to 180° the ground current vector is shifted by 180 degrees (change of sign), by device-internal
calculation, i.e. without modification of the wiring.
4.1.2
CT: Direct Controls
CT . CT Type
[Field Para / CT]
Relative
Relative, WE2 : 16 A ... 56 A, W2 : 16 A ... 56 A, W3 : 32 A ... 112 A,
W4 : 64 A ... 224 A, W5 : 128 A ... 448 A, W6 : 256 A ... 896 A
P.1
Select the connected CT Type (for the display of primary or relative phase current values).
CT . CT pri
[Field Para / CT]
0A
0A . . . 10000.0A
P.1
Nominal current of the primary side of the current transformers.
CT . ECT pri
[Field Para / CT]
60A
1A . . . 10000.0A
P.1
This parameter defines the primary nominal current of the connected earth current transformer. If the earth current
is measured via the Holmgreen connection, the primary value of the phase current transformer must be entered
here.
4.1.3
CT: Values
CT . IL1
[Operation / Measured Values / Current ]
Measured value: Phase current (fundamental)
CT . IL2
[Operation / Measured Values / Current ]
Measured value: Phase current (fundamental)
CT . IL3
[Operation / Measured Values / Current ]
Measured value: Phase current (fundamental)
18
WIC1
WIC1-1.0-EN-REF
4 Field settings
4.1.2 CT: Direct Controls