4
Field settings
4.1
CT – Current Transformer
4.1.1
CT: Settings
CT . Phase Sequence
[Field Para / General Settings]
ABC
ABC, ACB
P.1
Phase Sequence
CT . f
[Field Para / General Settings]
50Hz, 60Hz
P.1
Nominal frequency
CT . Measuring method
[Field Para / General Settings]
Fundamental
Fundamental, True RMS
P.1
Measuring method for the protection stages I>, I>>, I>>>, IG>, IG>>: Fundamental or RMS
CT . IG Source
[Field Para / General Settings]
If: Device Variant with Ground Current Inputs = True
• calculated, measured
•
If: Device Variant with Ground Current Inputs = False
• calculated
•
P.1
Selection if measured or calculated ground current should be used.
CT . Display of Meas. Values
[Field Para / CT]
Based on In,relative
If: CT . CT Type = Relative
• Based on In,relative
•
If: CT . CT Type ≠ Relative
• Based on In,relative, Primary current values
•
P.1
Select the preferred scaling/unit for the display of measurement values.
16
WIC1
WIC1-1.0-EN-REF
4 Field settings
4.1 CT – Current Transformer