7.13
I2> – Negative-Sequence Current Protection
7.13.1
I2>: Device Planning Parameters
I2> . Mode
[Device planning / Projected Elements]
“-”
“-”, use
P.1
Unbalanced Load-Stage, general operation mode
I2> . Definition
[Device planning / Definition]
Trip
Trip, Alarm
P.1
Unbalanced Load-Stage: If set to “Alarm”: The function operates as a supervision function, i.e. a fault generates
neither alarm nor trip, but an »Alarm« signal gets issued instead. If set to “Trip”: The function operates as a
protection function, i.e. trips the breaker in case of a fault.
7.13.2
I2>: Settings
I2> . Function
[Protection Para / I2>]
Active
Inactive, Active
P.1
Permanent activation or deactivation of module/stage.
I2> . I2
[Protection Para / I2>]
0.2In
0.2In . . . 2.5In
P.1
The Threshold setting defines a minimum operating current magnitude of I2 for the 46 function to operate, which
ensures that the relay has a solid basis for initiating a current unbalance trip. This is a supervisory function and not a
trip level.
I2> . Char
[Protection Para / I2>]
DEFT
DEFT . . . EF Curve
P.1
Characteristic
I2> . t
[Protection Para / I2>]
0.1s
Only available if:
• I2> . Char = DEFT
•
0.00s . . . 300.00s
P.1
Time delay for trip or alarm
55
WIC1
WIC1-1.0-EN-REF
7 Protection Parameter
7.13 I2> – Negative-Sequence Current Protection