TD_MRN3-3_08.06_GB
47
Function
Unit
Default settings
Actual
settings
Set1/Set2
Set1
Set2
U<4
4. Char. point_value 1
V 85/195/340/586*
U<4+t>
4. Char. point_value 2
s 3.00
U<5
5. Char. point_value 1 (U-voltage band)
V 85/195/340/586*
U<5+t>
5. Char. point_value 2 (End time)
s 3.00
tR
Permissible release time for characteristic curve 2
s 0.10
U1
Function of the 1
st
voltage step
U<
U1
Pick-up value for the 1
st
voltage step
V
85/195/340/586*
U1+t>
Tripping time for the 1
st
voltage step
s
5
U2
Function of the 2
nd
voltage step
U>
U2
Pick-up value for the 2
nd
voltage step
V
110/253/440/760*
U2+t>
Tripping time for the 2
nd
voltage step
s
1.00
U3
Function of the 3
rd
voltage step
U>
U3
Pick-up value for the 3
rd
voltage step
V
120/276/480/800*
U3+t>
Tripping time for the 3
rd
voltage step
s
0.10
T
Measuring repetition for frequency measuring
Periods
4
f
1
Pick-up value for the 1
st
frequency step
Hz
48.00
f
1
+t>
Tripping delay of the 1
st
frequency step
s
0.1
f
2
Pick-up value for the 2
nd
frequency step
Hz
47.50
f
2
+t>
Tripping delay for 2
nd
frequency step
s
0.1
f
3
Pick-up value for the 3
rd
frequency step
Hz
51.50
f
3
+t>
Tripping delay for 3
rd
frequency step
s
0.1
∆Θ
Pick-up value for vector surge
0
not active
1/3
Vector surge tripping logic
not active
df
Pick-up value for rate of change of df/dt
Hz/s
0.2
dt
Measuring repetition for df/dt
Periods
4
U
B
Voltage threshold for frequency measuring
V
10/23/40/68*
* Settings depending on the rated voltage 100 V/230 V/400 V or 690 V
Fault recorder
Default
Actual
Function
Unit
settings
settings
FR
Number of recordings
4
FR
Saving of the recording at the occurrence
TRIP
FR
Time prior to trigger impulse
s
0.05
"
Year setting
year
Y=00
"
Month setting
month
M=00
"
Day setting
day
D=00
"
Setting of the hour
hour
h=00
"
Setting of the minute
minute
m=00
"
Setting of the second
second
s=00