5.7   Additional 

functions 

 

5.7.1   Setting procedure for blocking of  
 

  the protection functions and  

 

  assignment of output relays 

 
The blocking function of the 

MRN3-3

    can be set ac-

cording to requirement. By applying the aux. voltage 
to D8/E8, the functions chosen by the user are 
blocked. Setting of the parameter should be done as 
follows: 
 

• 

When pressing push buttons <ENTER> and <TRIP> 
at the same time, message "BLOC" is displayed (i.e. 
the respective function is blocked) or "NO_B" (i.e. 
the respective function is not blocked). The LED allo-
cated to the first protection function Char1 lights 
green. 

• 

By pressing push buttons <+> <-> the value dis-
played can be changed. 

• 

The changed value is stored by pressing <ENTER> 
and entering the password. 

• 

By pressing the <SELECT/RESET> push button, any 
further protection function which can be blocked is 
displayed. 

• 

Thereafter the menu is left by pressing 
<SELECT/RESET> again. 

• 

If the <SELECT/RESET> key is actuated again, the 
blocking menu is left and the assignment mode is 
accessed. 

 

Function Description 

Display LED 

Char1 Undervoltage 

step 

BLOC green 

Char2 Undervoltage 

step 

BLOC green 

U1 Voltage 

step 

1 BLOC 

green 

U2 Voltage 

step 

2 NO_B 

green 

U3 Voltage 

step 

3 NO_B 

green 

f1 Frequency 

step 

BLOC 

green 

f2 Frequency 

step 

BLOC 

green 

f3 Frequency 

step 

NO_B 

green 

∆Θ

 

Vector surge 

BLOC 

green 

df/dt 

Frequency changing  
rate 

BLOC green 

Table 5.3: Blocking function for two parameter sets 

Assignment of the output relays: 

Unit 

MRN3-3

 has five output relays. The fifth output re-

lay is provided as permanent alarm relay for self su-
pervision and it is normally on. Output relays 1 - 4 are 
normally off and can be assigned as alarm or tripping 
relays to the protection functions which can either be 
done by using the push buttons on the front plate or 
via serial interface RS485. The assignment of the out-
put relays is similar to the setting of parameters, how-
ever, only in the assignment mode.  

The assignment mode can be reached only via the 
blocking mode. 
By pressing push button <SELECT/RESET> in blocking 
mode again, the assignment mode is selected. 
 
The LEDs Char1, Char2, U1, U2, U3, f1, f2, f3 and 

∆Θ

/df light up 

green

 when the output relays are as-

signed as 

alarm relays

 and LED t> 

red

 as 

tripping re-

lays

 

Definition:

 

Alarm relays

 are activated at pickup. 

Tripping relays

 are only activated after elapse of the 

tripping delay. 
 
After the assignment mode has been activated, first  
LED Char1 lights up green. Now one or several of the 
four output relays can be assigned to under voltage 
characteristic 1 as alarm relays. At the same time the 
selected alarm relays for under voltage characteristic 1 
are indicated on the display. Indication "1_ _ _" 
means that output relay 1 is assigned to this step. 
When the display shows "_ _ _ _", no alarm relay is 
assigned to this under voltage element. The assign-
ment of output relays 1 - 4 to the current elements can 
be changed by pressing <+> and <-> push buttons. 
The selected assignment can be stored by pressing 
push button <ENTER> and subsequent entry of the 
password. By pressing push button <SELECT/RESET>, 
LED Char1 lights up green and t> lights up red. The 
output relays can now be assigned to this element as 
tripping relays. 
 
Relays 1 - 4 are selected in the same way as de-
scribed before. By repeatedly pressing of the 
<SELECT/RESET> push button and assignment of the 
relays all elements can be assigned separately to the 
relays. The assignment mode can be terminated at any 
time by pressing the <SELECT/RESET> push button for 
some time (approx. 3 s). 

 
Note:

 

• 

The function of jumper J2 described in general de-
scription "MR Digital Multifunctional Relays" does not 
apply for 

MRN3-3

. For relays without assignment 

mode this jumper is used for parameter setting of 
alarm relays (activation at pickup or tripping). 

A form is attached to this description where the setting 
requested by the customer can be filled-in. This form is 
prepared for telefax transmission and can be used for 
your own reference as well as for telephone queries. 
 
 

Содержание HighTECH Line MRN3-3

Страница 1: ...MADE SIMPLE MAINS DECOUPLING RELAY WITH DF DT AND PROGRAMMABLE UNDERVOLTAGE CHARACTERISTICS HighTECH Line MAINS DECOUPLING RELAY WITH DF DT AND PROGRAMMABLE UNDERVOLTAGE CHARACTERISTICS Original docum...

Страница 2: ...etting parameters for under voltage characteristics 5 4 2 SYMmetrical ASYMmetrical or GENEral faults 5 4 3 Permissible release time for the under voltage characteristic curve 5 4 4 Plausibility check...

Страница 3: ...ns 6 5 4 Checking the operating and resetting values of the over underfrequency functions 6 5 5 Checking the tripping delay of the over underfrequency functions 6 5 6 Checking the vector surge functio...

Страница 4: ...been applied for the first time in protection technique is of enormous use for the accu rate identification and analysis of the grid state as demanded by the rules General Note For further technical d...

Страница 5: ...ccording to re quirement By applying the auxiliary voltage to D8 E8 the previously set relay functions are blocked refer to 4 8 and 5 7 1 3 1 3 Reset input Please refer to chapter 5 9 1 3 1 4 Output r...

Страница 6: ...cordings are chosen the relevant num ber of partial segments is reserved in the complete memory If the memory is full a new recording will always write over the oldest one Thus the fault recorder can...

Страница 7: ...t curve 1 warn Display shows no TRIP trip Display shows TRIP Char1 U 1 1 Char point_value 1 voltage value V 1 U Start 2 U Start Char1 U 1 t 1 Char point_value 2 not parameterisable s 0s fixed Char1 U...

Страница 8: ...voltage element V 1 200 1 460 4 800 tU2 U2 t Tripping time of the 2 nd voltage element s 0 04 290 U3 Function of the 3 rd voltage element U undervoltage U overvoltage U3 Pick up value of the 3 rd vol...

Страница 9: ...P2 and RS min and max are two coloured The LEDs on the left side next to the alphanumerical display light up green during measur ing and red during fault message The LEDs below the push button SELECT...

Страница 10: ...ompo nents caused by fault induced transients or other system disturbances The microprocessor continuously com pares the measured values with the preset thresholds stored in the parameter memory EEPRO...

Страница 11: ...generators consumers or electrical operating equip ment in general against over or underfrequency The relay has three independent frequency elements f1 f3 with individually adjustable parameters with...

Страница 12: ...protects the generator by tripping the generator circuit breaker in case of mains failure b Mains parallel operation and isolated single operation For this application the vector surge supervision tr...

Страница 13: ...verfunctions MRN3 3 should be connected separately to the busbar 4 7 Measuring principle of vector surge supervision When a synchronous generator is loaded a rotor dis placement angle is build between...

Страница 14: ...stable reference time and from this the deviation of the cycle duration of the voltage signal is ascertained In case of a vector surge as shown in fig 4 8 the zero passage occurs either earlier or lat...

Страница 15: ...st load change causing a vector surge and trips the mains C B For detecting high resistance mains failures a minimum current relay with an adjustable trip delay can be used A trip delay is needed to a...

Страница 16: ...ased Instantaneously released released instantane ously released after 1 s Released after 5 s released after 5 s 3 supply voltage is switched on blocked for 200 ms blocked for 200 ms blocked for 1 s b...

Страница 17: ...value in seconds SELECT RESET one time for each value Char1 U 5 Char1 U 5 t Permissible release time for under voltage limit curve 1 Setting value in seconds SELECT RESET one time for each value Char...

Страница 18: ...tive function Voltage threshold value for the frequency vector surge and df dt measurement setting value in Volt SELECT RESET f df Slave address of serial interface 1 32 SELECT RESET RS Baud Rate 1 12...

Страница 19: ...rameter the transformation ratio of the VT has to be set accordingly If the parameter is set to sec the measuring value indicated on the dis play is shown as rated secondary voltage Example The voltag...

Страница 20: ...or f 60 Hz The different designations f or v have no influence on any of the other functions All frequency functions are determined by setting the nominal frequency i e whether the set frequency thres...

Страница 21: ...order Figure 5 3 Function of digital inputs With the settings SET1 or SET2 the parameter set is acti vated by software Terminals C8 D8 and D8 E8 are then available as external reset input or blocking...

Страница 22: ...rts as soon as the failure occurs A fault in cident is detected when the voltage is below the threshold value U start and it will be stopped as soon as the voltage range U 5 had been exceeded At the m...

Страница 23: ...and the MRN3 3 detects a symmetrical fault then tripping will be blocked ALL means general fault If this function is assigned to an under voltage characteristic and the MRN3 3 de tects a fault then t...

Страница 24: ...marked accordingly in red 5 4 4 Plausibility check of the voltage characteristic The setting points are not independent from each other It is therefore recommended to parameterise them in ascending o...

Страница 25: ...value adjusted at T alarm is given and after the tripping delay of the frequency element has elapsed the tripping command is given The setting range for T is between 2 99 Recommendation for setting Fo...

Страница 26: ...ation Switching off and on of loads approx 20 of the nominal generator capacity must trip the relay Later in normal isolated operation the tripping of the relay is inhibited b In mains parallel operat...

Страница 27: ...ault recorder see chapter 3 1 5 Three parameters can be determined 5 5 1 Number of the fault recordings The max recording time is 20 s at 50 Hz or 16 66 s at 60 Hz The number of max recordings request...

Страница 28: ...can be changed and with ENTER be saved 5 6 Adjustment of the clock When adjusting the date and time LED lights up The adjustment method is as follows Date Year Y 00 Month M 00 Day D 00 Time Hour h 00...

Страница 29: ...how ever only in the assignment mode The assignment mode can be reached only via the blocking mode By pressing push button SELECT RESET in blocking mode again the assignment mode is selected The LEDs...

Страница 30: ...U1 t tripping X 1 _ _ _ U1 green t red U2 alarm X _ _ _ 4 U2 green U2 t tripping X 1 _ _ _ U2 green t red U3 alarm X _ _ _ 4 U3 green U3 t tripping X 1 _ _ _ U3 green t red f1 alarm X _ _ _ 4 f1 green...

Страница 31: ...ositive and negative df dt values occur but they do not cause any tripping due to the special measuring method These min max measurements are of great advan tage for long time analysis of the grid qua...

Страница 32: ...time the pa rameter set that is active at the occurrence is shown By pressing SELECT RESET the fault measuring values can be scrolled By pressing it can be scrolled back to a more recent fault data se...

Страница 33: ...of a protection function The display can only be reset when the pickup is not present anymore otherwise TRIP remains in display During resetting of the display the parameters are not affected 5 9 2 Er...

Страница 34: ...ternal blocking input terminals E8 D8 to inhibit the undervoltage functions and press the SELECT RESET for app 3 s to reset the LEDs and TRIP message 6 2 Testing the output relays and LEDs PLEASE NOTE...

Страница 35: ...t where three phase voltages are ap plied to the relay in Y connection MRN1 Versorgung Supply Versorgung Supply L L L N C9 E9 D9 Extern Reset External Reset Blockiereingang Blocking Input L L C8 L N D...

Страница 36: ...ent of the input signals the har monics will be rejected by the internal DFFT digital fil ter Whereas the RMS metering instrument measures the RMS value of the input signals 6 5 2 Checking the operati...

Страница 37: ...ckup values f1 f3 to EXIT For testing the pickup and dropout to pickup values the test frequency has to be increased decreased until the relay is energised This is indi cated by lighting up of LEDs f1...

Страница 38: ...hase angle obtained may be calculated with the following formula and is almost independent on the test voltages In case of a 3 phase vector surge the angle can be calculated with the following formula...

Страница 39: ...t Generally a primary injection test could be carried out in the similar manner as the secondary injection test described above With the difference that the pro tected power system should be in this c...

Страница 40: ...f 99 96 f 100 04 Dropout time 60 ms Time lag error class index E 10 ms Minimum operating time 40 ms Max allowed interruption of the auxiliary supply without a facting the function of the device 50 ms...

Страница 41: ...har 2 warn trip Voltage characteristics Char1 Char2 U Start Un 100 V EXIT 1 200 V Un 230 V EXIT 1 460 V Un 400 V EXIT 4 800 V Un 690 V EXIT 4 800 V 1 V 1 V 2 V 2 V 1 from setting value or 0 3 of UN U...

Страница 42: ...from setting value or 0 3 of UN tU 5 U 5 t tU 4 60s 0 02 0 06 1 00 0 05 1 00 2 00 0 1 2 00 5 00 0 2 5 00 10 0 0 5 10 0 20 0 1 20 0 50 0 2 50 0 60 1 related to the measured value of volt age resp 30 m...

Страница 43: ...50 01 70 Hz1 40 59 99 EXIT 60 01 80 Hz2 0 01 30 0 48 0 0 1 48 0 52 0 0 01 52 0 70 0 0 01 40 0 58 0 0 1 58 0 62 0 0 01 62 0 80 0 0 04 Hz 1 or 20 ms f1 t f3 t tf min 3 290 s EXIT 0 02 0 06 1 00 0 05 1 0...

Страница 44: ...recorder Function Parameter Adjustment example FR Number of recordings 1 x 20 s 1 2 x 10 s 3 4 x 5 s 7 8 x 2 5 s 50 Hz 1 x 16 66 s 1 2 x 8 33 s 3 4 x 4 16 s 7 8 x 2 08 s 60 Hz FR Saving of the record...

Страница 45: ...ision 1 step and vector surge 1 step Rated voltage 100 V Utilities Substation main substation 230 V direct connection without transformers 400 V direct connection without transformers 690 V direct con...

Страница 46: ...ristic 1 warn U 1 1 Char point_value 1 V 45 104 180 310 1 Char point_value 2 not changeable s U 2 2 Char point_value 1 V 45 104 180 310 U 2 t 2 Char point_value 2 s 0 16 U 3 3 Char point_value 1 V 70...

Страница 47: ...or frequency measuring Periods 4 f1 Pick up value for the 1 st frequency step Hz 48 00 f1 t Tripping delay of the 1 st frequency step s 0 1 f2 Pick up value for the 2 nd frequency step Hz 47 50 f2 t T...

Страница 48: ...l settings Default settings Actual settings Default settings Actual settings Char 1 cycle running Char 1 trip alarm X Char 2 cycle running X Char 2 trip alarm X U1 alarm X U1 t tripping X U2 alarm X U...

Страница 49: ...function X Code jumper Low High range for Reset input Low High range for blockage input Default settings Actual settings Default settings Actual settings Low plugged X X High not plugged All settings...

Страница 50: ...47884 Kempen Germany Telephone 49 0 21 52 145 1 Internet www SEGelectronics de Sales Telephone 49 0 21 52 145 331 Fax 49 0 21 52 145 354 E mail info SEGelectronics de Service Telephone 49 0 21 52 145...

Отзывы: