TD_MRN3-3_08.06_GB
7
3.2 Order of parameter settings
3.2.1 System
parameters
Setting parameter
Unit
Range
L1, L2, L3
Transmission ratio of the voltage transformers
SEK, 1.01...6500
∆
/Y
Input voltage correction depending on the input voltage
transformer connection
Y = star
DELT = Delta
fN
Adjustment of the rated frequency
Hz
50/60
∆Θ
/df
Selection vector surge or df/dt function
dPhi/dfdt
LED flashing after excitation
FLSH
FLSH/NOFL = flashing
NOFL = no flashing
P2
Parameter set change-over switch/Assignment of digital
inputs
Set1 = parameter set 1
Set2/2 = parameter set 2
FR = External triggering
B = External blocking
R = External Reset
SET 1
SET2
B_S2
R_S2
B_FR
R_FR
S2_FR
(refer to chapter 5.3.5)
3.2.2 Protection
parameters
Setting parameters
Unit
Range
Char1+U<Start
Start point of the limit curve 1
V
1–200/1–460/4–800*
Char1
Symmetrical, asymmetrical or general fault
SYM; ASYM, ALL
Char1
Under voltage limit curve 1
warn = Display shows no „TRIP“
trip = Display shows „TRIP“
Char1+U<1
1. Char. point_value 1
(voltage value)
V
1* - <= U<Start
2* - <= U<Start
Char1+U<1+t>
1. Char. point_value 2 (not parameterisable)
s
0s fixed
Char1+U<2
2. Char. point_value 1
(voltage value)
V
>= U<1–200*/>=U<1–
460*/
>=U<1–800*
Char1+U<2+t>
2. Char. point_value 2
(time value)
s
> U<1+t> - 60s
Char1+U<3
3. Char. point_value 1
(voltage value)
V
>= U<2–200*/
>=U<2–460*/>=U<2–800*
Char1+U<3+t>
3. Char. point_value 2
(time value)
s
> U<2+t> - 60s
Char1+U<4
4. Char. point_value 1
(voltage value)
V
>= U<3–200*/
>=U<3–460*/>=U<3–800*
Char1+U<4+t>
4. Char. point_value 2
(time value)
s
> U<3+t> - 60s
Char1+U<5
5. Char. point_value 1
(voltage value)
V
>= U<4–200* and
>= U<Start–200*/
>= U<4–460* and
>= U<Start–460*/
>=U< 4–800* and
>= U<Start–800*
Char1+U<5+t>
5. Char. point_value 2
(time value)
s
> U<4+t> - 60s
Char1+tR
Release time after voltage recovery 1
s
0.06 – 1.00s
Char2+U<Start
Start point the limit curve 2
V
1–200/1–460/4–800*
Char2
Under voltage limit curve 2
warn = Display shows no „TRIP“
trip = Display shows „TRIP“
Char2
Symmetrical, asymmetrical or general fault
SYM; ASYM, ALL
Char2+U<1
1. Char. point_value 1
(voltage value)
V
1* - <= U<Start
2* - <= U<Start