5.3.4 Display of the activation storage
(FLSH/NOFL)
If after an activation the existing current drops again
below the pickup value, e.g. U1 (provided, this step
was parameterised as under voltage step), without a
trip has been initiated, LED U< signals that an activa-
tion has occurred by flashing fast. The LED keeps flash-
ing until it is reset again (push button <RESET>). Flash-
ing can be suppressed when the parameter is set to
NOFL.
5.3.5 Parameterswitch/external
trigger
for the fault recorder
By means of the parameter-change-over switches it is
possible to activate two different parameter sets.
Switching over of the parameter sets can either be
done by means of software or via the external inputs
RESET or blocking input. Alternatively, the external in-
puts can be used for Reset or blocking and for the trig-
gering of the fault recorder.
Software-
parameter
Blocking input used
as
RESET input
used as
SET1
Blocking input
RESET input
SET2
Blocking input
RESET input
B_S2
Parameter switch
RESET input
R_S2
Blocking input
Parameter set
switch
B_FR
External triggering of
the fault recorder
Reset input
R_FR
Blocking input
External trigger-
ing of the fault
recorder
S2_FR
Parameter switch
External trigger-
ing of the fault
recorder
Figure 5.3: Function of digital inputs
With the settings SET1 or SET2 the parameter set is acti-
vated by software. Terminals C8/D8 and D8/E8 are
then available as external reset input or blocking input.
With the setting B_S2 the blocking input (D8, E8) is
used as parameter-set change-over switch. With the
setting R_S2 the reset input (D8, E8) is used as pa-
rameter-set change-over switch. With the setting B_FR
the fault recorder is activated immediately by using the
blocking input. On the front plate the LED FR will then
light up for the duration of the recording. With the set-
ting R_FR the fault recorder is activated via the reset
input. With the setting S2_FR parameter set 2 can be
activated via the blocking input and/or the fault re-
corder via the reset input. The relevant function is then
activated by applying the auxiliary voltage to one of
the external inputs.
With the setting R_FR the fault recorder is activated via
the reset input. With the setting S2_FR parameter set 2
can be activated via the blocking input and/or the
fault recorder via the reset input.
The relevant function is then activated by applying the
auxiliary voltage to one of the external inputs.
Important note:
When functioning as parameter change over facility,
the external input RESET is not available for resetting.
When using the external input BLOCKING the protec-
tion functions must be deactivated by software block-
ing separately (refer to chapter 5.7.1).