18
TD_MRN3-3_08.06_GB
Function
Display shows
Pressed pushbutton
Corresponding LED
Voltage threshold value U1
Tripping time delay tU1
Setting value in volt
Setting value in seconds
<SELECT/RESET> <+> <->
one time for each value
U3
U3+t>
rated frequency
setting value in Hz
<SELECT/RESET><+><->
f
N
frequency measuring repitition
setting value
<SELECT/RESET><+><->
T
frequency element f
1
tripping delay of frequency element f
1
setting value in Hz
setting value in seconds
<SELECT/RESET><+><->
one time for each value
f
1
f
1
+t>
frequency element f
2
tripping delay of frequency element f
2
setting value in Hz
setting value in seconds
<SELECT/RESET><+><->
one time for each value
f
2
f
2
+t>
frequency element f
3
tripping delay of frequency element f
3
setting value in Hz
setting value in seconds
<SELECT/RESET><+><->
one time for each value
F
2
f
3
+t>
1-OFF-3/3-OFF-3
Vector surge tripping
1Ph/3Ph <SELECT/RESET><+><->
1-3/dt
Pick-up value for Vector surge
Setting value in degree <SELECT/RESET><+><->
∆Θ
/df
df/dt pick-up value
df/dt measuring repetition
Setting value in Hz/s
Setting value in cycle
<SELECT/RESET><+><->
one time for each value
∆Θ
/df
1-3/dt
Blocking
EXIT
<+> until max. setting value
LED of blocked parameter
Blocking of a protection step via
digital input
BLOC/NO_B
<SELECT/RESET><+><->
LED of the blocking
protection function
Relay assignment
_ _ _ _ /
1_ _ _ 1 2 3 4
<SELECT/RESET><+><->
LED of the assigned
protective function
Voltage threshold value for the
frequency, vector surge and df/dt
measurement
setting value in Volt
<SELECT/RESET><+><->
f,
∆Θ
,
df
Slave address of serial interface
1 - 32
<SELECT/RESET><+><->
RS
Baud-Rate
1)
1200-9600 <SELECT/RESET>
<+><->
RS
Parity-Check
1)
even odd no
<SELECT/RESET> <+><->
RS
Recorded fault data:
star--connection: U1, U2, U3
tripping values in Volt
<SELECT/RESET><+><->
one time for each phase
L1, L2, L3, U1, U2, U3
delta-connection:
U12, U23, U31
tripping values in Volt
<SELECT/RESET><+><->
one time for each phase
L1, L2, L3, U1, U2, U3
frequency
tripping values in Hz
<SELECT/RESET><+><->
one time for each phase
f, f
1
, f
2
, f
3
, f
min
,
f
max
rate of change of frequency
tripping value in Hz/s
<SELECT/RESET><+><->
∆Θ
/
df
Vector surge angle at tripping
tripping value in degree <SELECT/RESET><+><->
∆Θ
+ L1, L2 or L3
Enquiry failure memory
FLT1; FLT2.....
<-><+>
L1, L2, L3, U1, U2, U3,
f
1
, f
2
, f
3
,
∆Θ
/
df
Save parameter?
SAV?
<ENTER>
Save parameter!
SAV!
<ENTER> for about 3 s
Trigger signal for the fault
recorder
TEST, P_UP, A_PI, TRIP
<SELECT/RESET> <+><->
FR
Number of fault occurrences at
50 Hz
1=20; 2=10; 3=5;
4=5; 7=2; 8=2
<SELECT/RESET> <+><->
FR
Number of fault occurrences at
60 Hz
1=16; 2=8; 3=4; 4=4;
7=2; 8=2
<SELECT/RESET> <+><->
FR
Display of date and time
Y=99, M=10, D=1,
h=12, m=2, s=12
<SELECT/RESET> <+><->
"
Software version
First part (e.g. D02-)
Sec. part (e.g. 6.01)
<TRIP>
one time for each part
Manual trip
TRI?
<TRIP> three times
Inquire password
PSW?
<SELECT/RESET>/
<+>/<->/<ENTER>
Relay tripped
TRIP
<TRIP> or fault tripping
Secret password input
XXXX
<SELECT/RESET>/
<+>/<->/<ENTER>
System reset
SEG
<SELECT/RESET> for about 3 s
1)
only Modbus
Table 5.1: Possible indication messages on the display