SecuriLan network units and MIC711
Mounting and installation, Technical Description, T 811 086 en e
93 / 128
9.5.4
SecuriLan connection with 10/100TX interface
The distance between two directly connected control panels via the 10/100TX interface is limited to 100 m if no auxiliary de-
vices are used.
X4
B6-NET2-485
X2
5
6
RS 485
10/100
X4
B6-NET2-485
X2
5
6
RS 485
10/100
Fig. 115 SecuriLan connection with 10/100TX interface
Board /
Unit
Used
interfaces
B5-NET4-485
X2 [0B] or X2 [0A]
B5-NET2-485
X2 [0B] or X2 [0A]
B6-NET2-485
X2
B5-NET2-FX
X2 [0B] or X2 [0A]
B6-NET2-FX
X2
B5-LAN
X2
B6-LAN
X2
B5-MIC711
X3
B6-MIC711
X3
Notice
A redundant connection with a B6-NET2-485, B6-NET2-FX and B6-LAN is not possible!
9.5.5
SecuriLan connection via Ethernet network (logical connection)
Integrating PC applications is possible via a standard Ethernet. Further, SecuriFire SCPs can also be networked via a stan-
dard Ethernet. This type of network is possible only when non-redundant.
X4
B
6
-N
E
T
2
-4
8
5
X2
5
6
RS 485
10/100
B
6
-L
A
N
X2
10/100
B5-LAN
X3
X2
B
A/B
10/100
10/100
Fig. 116 Non-redundant network
Board /
Unit
Used
interfaces
B5-NET4-485
X2 [0B] or X2 [0A]
B5-NET2-485
X2 [0B] or X2 [0A]
B6-NET2-485
X2
B5-NET2-FX
X2 [0B] or X2 [0A]
B6-NET2-FX
X2
B5-LAN
X2
B6-LAN
X2
B5-MIC711
X3
B6-MIC711
X3
Notice
This connection option is not standards-compliant for SCPs and therefore permitted only for PC applications,
since components without VdS device approval (e.g. switches) are used.