EPI-BUS devices
Mounting and installation, Technical Description, T 811 086 en e
81 / 128
8.8
B5-EPI-PIM partial indication map
Via the
Extended Bus
(EPI-BUS) by means of a patch cable and an
8-pin RJ45 plug, the partial indication map can be connected to any
SecuriFire MIC11 / MIC711 as well as to the B5-MMI-FIP and B5-
MMI-IPS devices.
Additional EPI devices can be connected to the second RJ45.
The B5-EPI-PIM is mounted either on the door of the SecuriFire or
immediately next to a remote SecuriFire indication and control
map.
Via the hex coding switch you can set one of the three possible
EPI-BUS addresses. For each MMI-BUS participant with an EPI-
BUS interface, up to three EPI devices can be connected.
More information about the B5-EPI-PCM can be found in the Tech-
nical Description T 811 084.
Fig. 103 B5-EPI-PIM
8.8.1
Interfaces
EPI Port A “INCOMING”
EPI Port B “OUTGOING”
Designation
Terminal
Terminal
Designation
GNDP
1
2
VP
3
4
EXTBUS-
+3V3
5
6
+3V3
GNE
7
8
GND
8.8.2
Technical data
Operating voltage:
3,3 V
Quiescent current:
5 mA
Data transmission:
Electrical:
EPI-BUS
RS485
Distance to the MIC main indication and control map: max. 1 m
Protection class:
IP 30
Ambient temperature:
-5 °C to +50 °C
Dimensions:
Dimensions without map case:
170 x 138 x 48 mm (W x H x D)
85 x 70 x 20 mm (W x H x D)
Map case colour:
grey
8.8.3
Compatibility information
SecuriFire Studio
from release 1.2
EPI interface
B5-MIC (all versions), B6-MIC (all versions)
B5-MMI-FIP, B5-MMI-IPS
Notice
From which side the EPI bus “INCOMING” or
“OUTGOING” is connected is not relevant.
For purposes of clarity, however, we recommend
continuing with one connection system once be-
gun.