Annex
122 / 128
Mounting and installation, Technical Description, T 811 086 en e
12.5
Connection of FSS 800-1 fire brigade key box
Commissioning the safe and adapter is based on the mounting and commissioning instructions of the FSS 800-1 fire brigade
key box.
Warning
Prior to commissioning, all closing cylinders must be deployed and their keys must be available. If this is not
the case at the time of commissioning, suitable replacement cylinders must be used; they will then be ex-
changed later for the final cylinders.
The supplied conical arrester pin for the cover lid of the fire brigade lock is mounted only after the FSS 800-1
fire brigade key box and AD 800-1 adapter are fully functional.
The lock striker plate safeguard of the customer lock is a Z-angle made of plastic which is placed in the door. It
can be removed only after the FSS 800-1 fire brigade key box and AD 800-1 adapter are fully functional.
Connection diagram
F
ir
e
b
ri
g
a
d
e
k
e
y
b
o
x
F
ir
e
b
ri
g
a
d
e
k
e
y
b
o
x
a
d
a
p
te
r
Operating voltage
YSCH 10 x 0,6
or 5 x 2 x 0.6
4 x 0.6
Fire alarm
feedback
AD 800-1
FSS 800-1
VExt
GNDExt
B6-PSU
5
9
1
2
6
10
4
8
12
3
7
11
5
9
1
2
6
10
4
8
12
3
7
11
13
17
21
14
18
22
16
20
24
15
19
23
B6-BCB
RX
RX
X11
X5
Fig. 175 FSS 800-1 connection diagram
Setting the jumpers on the AD 800-1 adapter
Fig. 176 JP1
Place jumper JP1 on position 1
–2 (= factory setting). With jumper JP1 you can select whether the trigger
contact on the fire alarm control panel is closed in the event of a trigger (position 1
–2) or open (position
2-3). In any case, one of the positions must be selected; the jumper may not be removed.
Fig. 177 JP2
Place jumper JP2 (= factory setting). With jumper JP2 you can select whether for the trigger a potential-
free contact (jumper closed) or a voltage of 11 to 30 VDC is used.
Fig. 178 JP3
Remove jumper JP3. If jumper JP3 is placed, the heating voltage display is included in the fault evalua-
tion.