MMI-BUS devices
Mounting and installation, Technical Description, T 811 086 en e
67 / 128
7.5
B5-MMI-FPS-S Fire brigade panel Sweden
The fire brigade panel Sweden can be connected via the MMI
bus to the main control unit board B6-BCB12/13 of the Se-
curiFire 1000/2000.
The B5-MMI-FPS-S can be remotely mounted up to 1200 m
from the SecuriFire 1000/2000.
With the hex coding switch you can set one of fifteen possible
MMI bus addresses.
More information about the B5-MMI-FPS-S can be found in
Technical Description T 811 132.
Fig. 90 B5-MMI-FPS-S
7.5.1
Interfaces
X1
Connection for MMI bus data
X2
Connection for MMI bus power supply
X3
Connection for LC display
X31
Connection for LC display lighting
X4/X6
Jumper for MMI bus termination
if jumpers are connected, the MMI bus is terminated
X5
EPI bus
X7
Jumper for audible of indication and control map
if the jumper is connected the audible is deactivated
X8
Jumper for reset of indication and control map
DO ALWAYS REMOVE !
S1
Rotary switch for MMI bus address
Fig. 91 B5-MMI-FPS interfaces
7.5.1.1
MMI bus power supply connector plug (X1) and power supply (X2)
X1
MMI bus connector plug
X2
power supply
X1
1
MMI-BUS
B cabel
MMI-BUS
A cabel
2nd core pair
or shield
2nd core pair
or shield
X2
1
MMI power supply A
MMI power supply B
MMI+24VA
MMI+24VB
MMI+24VA
MMI+24VB
MMIGNDA
MMIGNDB
MMIGNDA
MMIGNDB
+BUS-B
+BUS-A
-BUS-B
-BUS-A
GNDISO
GNDISO
GNDISO
GNDISO
+BUS-A
+BUS-B
-BUS-B
-BUS-A
Terminal
Designation
Terminal
Designation
1
GNDISO
1
MMIGNDB
2
-BUS-A
2
MMI+24VB
3
+BUS-A
3
MMIGNDB
4
GNDISO
4
MMI+24VB
5
-BUS-A
5
MMIGNDA
6
+BUS-A
6
MMI+24VA
7
GNDISO
7
MMIGNDA
8
-BUS-B
8
MMI+24VA
9
+BUS-B
10
GNDISO
11
-BUS-B
12
+BUS-B
Fig. 92 MMI bus power supply connector plug (X1) and power supply (X2)