Expansion units for SecuriFire 2000
52 / 128
Mounting and installation, Technical Description, T 811 086 en e
6.18.1
Technical data
Unit
Voltage supply:
via SecuriFire 2000 main control unit
Supply voltage:
+22 V to +30 V
Power consumption:
1.35 mA (without detector)
Monitored outputs:
8
Monitored inputs / detection zones:
Number
10
Line length
max. 1000 m
Ambient temperature:
-5°C to +50°C
Rel. air humidity:
5% to 95%, without condensation
Monitored inputs / detection zones
Supply voltage:
min. 22 V
typically 24 V
max. 28 V
Short-circuit current:
min. 170 mA
typically 199 mA
max. 288 mA
Cable resistance:
50
max.
Cable capacity:
120 nF max.
Coverage:
= 1.0 mm
1,100 m max.
= 0.8 mm
720 m max.
= 0.6 mm
400 m max.
Monitored outputs:
Supply voltage:
min. 22 V
typically 24 V
max. 28 V
Output current:
max. 1.5 A
Short-circuit current:
min. 1.77 A
typically 2.17 A max. 3.14 A
Load range:
Range 1
354
to
1,000
Range 2
70
to
354
Range 3
20
to
70
Line resistance:
Range 1
50
max.
Range 2
20
max.
Range 3
5
max.
6.18.2
Compatibility information
Compatible main control unit:
B6-BCB13
SecuriFire-Studio:
from release 1.1