System overview
14 / 128
Mounting and installation, Technical Description, T 811 086 en e
Earthing concept
The earthing concept used in the SecuriFire 1000/2000 with central protection earthing to protect persons and electronics re-
quires that all electrically charged components connected to the GND line of the SecuriFire 1000/2000 control panel may be
installed only in areas and buildings which have regulation-complaint potential equalization.
Warning
Non-observance can cause malfunctions and/or damage the control panel and may endanger people.
Software
The SecuriFire 1000/2000 microprocessor-controlled system is equipped with a multitasking-capable, real-time operating
system. A basic function program is loaded into the system and is adjusted to the object to be protected by means of cus-
tomer-specific programming while taking into consideration relevant applicable standards.
Notice
This document applies to SRP 2.0 (SecuriFire Release Package) and later.
It is always recommended to use the most recent SecuriFire Studio release.
Important features
Microprocessor-controlled and monitored system technology.
Continual, automatic check routines for all system components and programs.
Units connected easily with blade connector.
Up to 31 external main indication and control maps per SecuriLan with graphic display; up to 4 languages can be toggled
during operation.
Integrated protocol printer with emergency power supply and event memory with message filter.
Suitable for connection to the public alarm system of the fire brigade.
Can be connected to superordinate computer systems and fire alarm deployment management systems via a serial inter-
face protocol with full functional scope (alarm/command directions).
Fully redundant interconnection of up to 16 control panels without superordinate central computer.
Superordinate networking of nearly any number of fire alarm control panels (also subsequently).
A maximum of 250 participants per loop and loop length of up to 3,500 m.
Main indication and control maps, protocol printers, parallel indicator boards and other system components are con-
nected by digital communication lines and can be deployed in any combination irrespective of location with any control
panel.
This complies with the following standards and directives: European standards EN 54, DIN, ÖNORM, ÖVE and VDE.
VdS devices and system approval (G209049, S209049, G209047, G209048, S209047).