Main control units
36 / 128
Mounting and installation, Technical Description, T 811 086 en e
5.3.10
SecuriLine eXtended
One or two addressable loops and the associated detectors and modules of the SecuriLine eXtended technology can be
connected to each SecuriFire 1000/2000 main control unit (B6-BCB12 and B6-BCB13) as well as to the B4-DAI2 and B6-
LXI2 SecuriLine unit.
Further information about the main control units or unit can be found in the following technical documentation:
B6-BCB12
T 811 032
B6-BCB13
T 811 031
B4-DAI2
T 811 035
B6-LXI2
T 811 067
Notice
The B4-DAI2 meets the specification of the SecuriLine but not that of the SecuriLine eXtended. In addition to the
SecuriLine modules, SecuriLine eXtended modules which support the SecuriLine mode can be operated on the
B4-DAI2 trouble-free.
Warning:
Some BX modules cannot be operated on a SecuriLine (e.g. BX-O2I4).
The SecuriLine specifications always apply.
There is no reference to the BA modules in this document, since at the time of this product release only BX
modules are being sold.
5.3.11
Connector plug for SecuriLine eXtended
B6-BCB12 and B6-BCB13 (X12) or B4-DAI2 (X2)
Loop no.
Designation
Function
2
V4
Not present
G4
Screen
C4
GND loop end
L4
+24V loop end
V3
Not present
G3
Screen
C3
GND loop beginning
L3
+24V loop beginning
1
V2
Not present
G2
Screen
C2
GND loop end
L2
+24 V loop end
V1
Not present
G1
Screen
C1
GND loop beginning
L1
+24 V loop beginning
5.3.12
Technical data
Connection:
2 addressable loops, each max. 250 participants or 4 stub lines, each max. 125 partici-
pants
Short-circuit isolator:
integrated in detectors and modules
Line voltage:
30 V ±5%
Rated current:
max. 150 mA (addressable loop), max. 75 mA (stub line)
Short-circuit current:
max. 232 mA
Loop interface:
16-pin plug-in screw termination on the front side
Loop and stub line lengths:
max. 3,500 m
Notice
The properties of the SecuriLine eXtended (e.g. 250 participants per loop) apply only when SecuriLine eXtended
elements are used. Since the SecuriLine eXtended elements are backwards compatible, mixed operation with
elements of SecuriLine is also possible; in this case, however, the performance features of the conventional Se-
curiLine apply to the loop!