Doc. No.: A05280692 Rev. AE ECO: 13200 Date: 11/04/2019
53
Delayed Egress Activation Time
Each ID Exit Panel controlling an electromagnetic lock has a required time period for pressure applied to a door to activate
the delayed egress release feature as required by NFPA 101. Refer to the NFPA 101 Life Safety Code or your local Fire
Marshall/Safety Inspector for guidance on local requirements. This feature allows you to modify the time necessary to
apply the constant even pressure upon the door to activate the delayed egress alarm mode. The four options below are 3
sec., 2 sec., 1 sec., and 0 sec. Changing the activation time from factory default should be done only after permission is
granted by the local authority having jurisdiction.
Delayed Egress Activation Time
Factory Default
3 Seconds
To
change
the activation time to
3 seconds
, follow the three listed steps without pausing for greater than one
second between keystrokes.
1.
Enter
*567
or currently programmed secondary code
2.
Enter
*9876543217#753
Three confirmation beeps = change accepted
No confirmation beep = change not accepted
To
change
the activation time to
2 seconds,
follow the three listed steps without pausing for greater than one
second between keystrokes.
1.
Enter
*567
or currently programmed secondary code
2.
Enter
*9876543217#852
Two confirmation beeps = change accepted
No confirmation beep = change not accepted
To
change
the activation time to
1 second,
follow the three listed steps without pausing for greater than one
second between keystrokes.
1.
Enter
*567
or currently programmed secondary code
2.
Enter
*9876543217#951
One confirmation beep = change accepted
No confirmation beep = change not accepted
To
change
the activation time to
0 seconds,
follow the three listed steps without pausing for greater than one
second between keystrokes.
1.
Enter
*567
or currently programmed secondary code
2.
Enter
*9876543217#580
Four confirmation beeps = change accepted
No confirmation beep = change not accepted
Beeping during the nuisance section of delayed egress is now selectable.
(Default setting is nuisance noisy)
To make nuisance quiet enter
*567*9876543217#777
To make nuisance noisy enter
*567*9876543217#707
SECTION 10 PROGRAMMING INSTRUCTIONS
Содержание KinderGUARD ID
Страница 8: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 8...
Страница 9: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 9...
Страница 10: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 10...
Страница 75: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 75...
Страница 77: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 77...
Страница 78: ...Doc No A05280692 Rev AE ECO 13200 Date 11 04 2019 78...