4.2.2
Protecting people and equipment
4.2.2.1.
Earthing system principle
The
Earthing system
, or
SLT
(formerly
Neutral system
) of the electrical installation defines the situation of the generating set neutral
in relation to earth and the grounds of the electrical installation at the user end.
Our generating sets are designed to operate with the TT system (or EDF application depending on the option, for France only).
4.2.2.2.
TT
system
In the TT earthing system, automatic power cut-off via a Residual Current Device (RCD) is obligatory at the upstream part of the
installation, to ensure that personnel are protected (additionally, a maximum 30 mA device must be installed on outlet circuits).
Figure 15 :
TT earthing system
The alternator neutral is earthed, the grounds of the user equipment have their own earth connection.
R
Ph 1
Ph 2
Ph 3
N
PE
R
R
Neutral connected
to earth
T
Ground connected
to earth
T
Neutral earth
Ground earth
R
Ph 1
Ph 2
Ph 3
N
PE
R
id
id
id
Equipment
39/242
Содержание R33C3
Страница 2: ......
Страница 61: ...The following diagram shows the structure of the main menu and how to go to each parameter 59 242 ...
Страница 94: ...92 242 ...
Страница 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Страница 96: ...94 242 ...
Страница 98: ...96 242 ...
Страница 115: ...113 242 ...
Страница 135: ...133 242 ...
Страница 145: ...143 242 ...
Страница 179: ...177 242 ...
Страница 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Страница 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Страница 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Страница 194: ...192 242 ...
Страница 196: ...194 242 ...
Страница 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Страница 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Страница 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...