Installation and maintenance
R438
A.V.R.
3.3 - Electrical faults
Fault
Action
Effect
Check/Cause
No voltage at
no load on
start-up
Connect a new battery
of 4 to 12 volts to
terminals E- and E+,
respecting the polarity,
for 2 to 3 seconds
The alternator builds up and its
voltage is still correct when the
battery is removed.
- Lack of residual magnetism
The alternator builds up but its
voltage does not reach the rated
value when the battery is
removed.
- Check the connection of the voltage
reference to the AVR
- Faulty diodes
- Armature short-circuit
The alternator builds up but its
voltage disappears when the
battery is removed
- Faulty AVR
- Field windings disconnected
- Main field winding open circuit - check the
resistance
Voltage too
low
Check the drive speed
Correct speed
Check the AVR connections (AVR may be
faulty)
- Field windings short-circuited
- Rotating diodes burnt out
- Main field winding short-circuited - Check
the resistance
Speed too low
Increase the drive speed
(Do not touch the AVR voltage pot. (P2)
before running at the correct speed.)
Voltage too
high
Adjust AVR voltage
potentiometer
Adjustment ineffective
Faulty AVR
Voltage
oscillations
Adjust AVR stability
potentiometer
If no effect : try normal / fast
recovery modes (ST2)
- Check the speed : possibility of cyclic
irregularity
- Loose connections
- Faulty AVR
- Speed too low when on load (or U/F bend
set too high)
Voltage
correct at no
load and too
low when on
load (*)
Run at no load and
check the voltage
between E+ and E- on
the AVR
Voltage between E+ and E-
SHUNT < 20 V
AREP / PMG < 10V
- Check the speed (or U/F bend set too
high)
Voltage between E+ and E-
SHUNT > 30V
AREP / PMG > 15V
- Faulty rotating diodes
- Short-circuit in the main field. Check the
resistance
- Faulty exciter armature.
(*) Caution :
For single-phase operation, check that the sensing wires coming from the AVR are correctly connected to the
operating terminals
Voltage
disappears
during
operation (**)
Check the AVR, the
surge suppressor, the
rotating diodes, and
replace any defective
components
The voltage does not return to the
rated value.
- Exciter winding open circuit
- Faulty exciter armature
- Faulty AVR
- Main field open circuit or short-circuited
(**) Caution :
Internal protection may be activated (overload, open circuit, short-circuit)
Warning : after operational testing,
replace all access panels or covers.
3971 en -
238/242
Содержание R33C3
Страница 2: ......
Страница 61: ...The following diagram shows the structure of the main menu and how to go to each parameter 59 242 ...
Страница 94: ...92 242 ...
Страница 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Страница 96: ...94 242 ...
Страница 98: ...96 242 ...
Страница 115: ...113 242 ...
Страница 135: ...133 242 ...
Страница 145: ...143 242 ...
Страница 179: ...177 242 ...
Страница 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Страница 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Страница 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Страница 194: ...192 242 ...
Страница 196: ...194 242 ...
Страница 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Страница 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Страница 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...