LEROY-SOMER
9
2010.11 / f
Installation and maintenance
R438
A.V.R.
3 - INSTALLATION - COMMISSIONING
3.1 - Electrical checks on the AVR
- Check that all connections have been
made properly as shown in the attached wi-
ring diagram.
- Check that the ST3 frequency selection
jumper is on the correct frequency setting.
- Check whether the ST4 jumper or the re-
mote adjustment potentiometer have been
connected.
- Optional operating modes.
• ST1 jumper : open to connect the R 731or
R 734 3-phase
sensing module.
• ST2 jumper : open if rapid response time
used
• ST5 jumper : open to suppress the LAM
function.
3.2 - Settings
The machine is tested and set at the fac-
tory. When first used with no load, make
sure that the drive speed is correct and
stable (see the nameplate). After opera-
tional testing, replace all access panels
or covers.
The only possible adjustments to the
machine should be made on the AVR.
3.2.1 - R438 settings (AREP or PMG
system)
Before any intervention on the A.V.R.,
make sure that the ST9 jumper is closed
with AREP excitation and disconnected
with PMG or SHUNT or separate excita-
tion.
a)
Initial potentiometer settings (see table
below)
- Remote voltage adjustment potentiometer :
centre (ST4 jumper removed).
Stability adjustments in standalone
operation
b
) Install a D.C. analogue voltmeter (needle
dial) cal. 50V on terminals E+, E- and an
A.C. voltmeter cal 300 - 500 or 1000V on the
alternator output terminals.
c
) Make sure that the
ST3
jumper is positio-
ned on the desired frequency (50 or 60 Hz).
d
) Voltage potentiometer
P2
at minimum,
fully anti-clockwise.
e
) Stability potentiometer
P3
to around 1/3
of the anti-clockwise limit.
f
) Start the engine and set its speed to a fre-
quency of 48 Hz for 50 Hz, or 58 for 60 Hz.
g
) Set the output voltage to the desired va-
lue using
P2
.
- Rated voltage UN for solo operation (eg.
400 V)
- Or UN + 2 to 4% for parallel operation with
C.T. (eg. 410 V)
If the voltage oscillates, use P3 to make ad-
justments (try both directions) observing the
voltage between E+ and E- (approx. 10V
D.C.).
WARNING
P2
P3
P1
P5
10 A
maximum
400V - 50 Hz
(Input
0 - 380 V)
Not set
(centre position)
Not set
(fully anti-
clockwise)
Excitation ceiling
Limit of excitation and
short-circuit current,
minimum fully anti-clockwise.
Voltage quadrature droop
(// operation with C.T.)
- 0 quadrature loop fully
anti-clockwise.
Voltage
minimum fully anti-clockwise
Stability
Action
Factory setting
Pot.
3971 en -
235/242
Содержание R33C3
Страница 2: ......
Страница 61: ...The following diagram shows the structure of the main menu and how to go to each parameter 59 242 ...
Страница 94: ...92 242 ...
Страница 95: ...10 Appendix 10 1 Appendix A Engine user and maintenance manual 93 242 ...
Страница 96: ...94 242 ...
Страница 98: ...96 242 ...
Страница 115: ...113 242 ...
Страница 135: ...133 242 ...
Страница 145: ...143 242 ...
Страница 179: ...177 242 ...
Страница 191: ...July 2009 Pub No 99610 29120 OPERATION MAINTENANCE MANUAL 189 242 ...
Страница 192: ...Printed in Japan Pub No 99610 29120 190 242 ...
Страница 193: ...10 2 Appendix B Alternator user and maintenance manual 191 242 ...
Страница 194: ...192 242 ...
Страница 196: ...194 242 ...
Страница 227: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 225 242 ...
Страница 242: ...14 LEROY SOMER 2010 11 f Installation and maintenance R438 NOTES 3971 en 240 242 ...
Страница 243: ...LEROY SOMER 15 2010 11 f Installation and maintenance R438 NOTES 3971 en 241 242 ...