There are four primary components to be installed:
1.
The Keypad
should be mounted on the wall adjacent to the door. It should be on the
same side as the door strike and about 4 feet above the floor.
2.
The Control Module
should be mounted inside the building near a power source.
Typically the control module is hidden in a false ceiling or closet. The control module must
be located in an area where the temperature remains between -40°F and 120°F
(-40°C and +49°C).
3.
The Wiring Cable
connects the keypad to the control module. It is important not to locate
the cable adjacent to any wiring that carries line voltage. Included with the system is a 15-
foot 12 conductor jacketed wiring cable of which only 8 wires are used. If the Control
Module must be located further than 15 feet from the Keypad, additional cable may be
spliced. The maximum distance between the Keypad and the Control Module must not
exceed 1,000 feet. For runs over 200 feet, 18 gauge wire should be used. Under 200 feet,
20 gauge is acceptable.
4.
The Electric Strike/Other Locking Device
(not included) connects to the 936’s Relay
output(s) via the strike cable. (See Typical Wiring Diagrams pg 22). Please refer to the
installation instructions included with your locking device for specific mounting directions.
THE INSTALLATION PROCEDURE
REQUIRED TOOLS
You will need the following tools:
• Medium Phillips screwdriver
•
⅛
" standard screwdriver
• Drill
•
⅞
” or 1” (25mm) drill bit
• ½" (13mm) drill bit
•
5
/
32
" (4mm) drill bit
936 EntryCheck
™
SYSTEM COMPONENTS
PREPARING FOR INSTALLATION
P:\INSTALLATION INST\Access Control\INST-936.vsd 0106 Page 5